Maintenance

29

11.2 AC Power Connections

Power connections may be disconnected from the UPS cabinet via a removable distribution box. This 

may be a convenient feature if the UPS must be moved a short distance or replaced. This box allows 

power connections to be conveniently disconnection from the main UPS cabinet. A label is attached to 

the UPS to describe these procedures.

11.2.1 Disconnect

1. DO NOT turn off the branch circuit breaker feeding power the box unless you intend to disconnect 

all power to the load.

2. Ensure that the Maintenance Bypass Lamp is ON.
3. Switch to the maintenance bypass position.

The load is now unprotected from line disturbances or interruptions.

4. Turn off the UPS using the front panel controls.

a. If needed, push the OFF button for one second once to transfer the load to bypass.
b. Press the OFF button twice within four seconds to turn the UPS off.

5. Turn off the UPS input circuit breaker on the box at the rear of the UPS.

This input circuit breaker cuts off power only from the connector between the box and UPS. The 

input circuit breaker does not cut off power from the manual bypass switch.

6. Turn off the output circuit breaker on the rear of the UPS.
7. Remove the distribution box from the UPS

a. Loosen all three captive screws until the box releases.
b. Pull box away from the UPS and set the box aside on a padded surface.

8. Loosen the cover over the electrical connections by backing out the three screws one turn each.
9. Slide the cover over the electrical connections.
10. Gently retighten the three screws loosened in 

Step 8

.

Whenever the power distribution box is not attached to the UPS, the cover must be slid over the 

electrical connections to prevent damage or injury.

Figure 8

Power distribution box, PD-L630

!

CAUTION

Power is still passing through the power distribution box from the utility supply to the load. 

OUTPUT
BREAKER

20A 240V~/T

OUTPUT
BREAKER
20A 240V~/T

ON

ON

INPPUT

OUTPUT ONLY  CB DO

ES NOT

CONNECT BYPASS POW

ER TO

MANUAL BYPASS SW

ITCH.

BREAKER 30A

ON

OFF

OFF

OFF

UPS

UTILITY

MAITANENCE BYPASS

AVAILABLE

UPS

AVAILABLE

C

O

NNECT

OR PRO

T

ECTIVE C

O

VER  DO NO

T REMOVE SCRE

WS

PRIOR 

T

O

 INST

ALLA

T

ION OF BO

X ON UPS

-L

OOSEN THREE 

SCRE

WS 

1 TURN

- SLIDE C

O

VER 

T

O

 EXPOSE C

O

NNECT

OR

-TIGHTEN SCRE

W

S GENTL

Y

UPON REMOV

A

L OF BO

X FROM UPS

-L

OOSEN THREE 

SCRE

WS 

1 TURN

-SLIDE C

O

VER 

T

O

 REA

CH END SCRE

W AND C

O

VER C

O

MMUNICA

T

ION

-TIGHTEN SCRE

W

S GENTL

Y

Maintenance 

Bypass Lamps

Maintenance 

Bypass Switch

Captive 

Screws 

(attach 

box to 

UPS)

Rear View

Front View

Protective 

Cover Over 

Connectors

Содержание GXT2-6000RTL630

Страница 1: ...AC Power For Business Critical Continuity Liebert GXT2 6000RTL630 User Manual 208 240 VAC...

Страница 2: ......

Страница 3: ...5 1 2 Rack Mount UPS Installation 12 5 1 3 Installing the Adjustable Rack Mount Kit Sold Separately 12 5 2 Install the Internal Batteries 14 5 3 Connect the Internal Batteries Using the External Conne...

Страница 4: ...TROUBLESHOOTING 31 12 0 1 Auto Learning Battery Run Times 35 13 0 SPECIFICATIONS 36 FIGURES Figure 1 GXT2 6000RTL630 front view 7 Figure 2 GXT2 6000RTL630 rear view 8 Figure 3 Internal battery pack wi...

Страница 5: ...sive substances This UPS contains no user serviceable parts except the internal battery pack The Off Bypass push button does not electrically isolate internal parts Under no circumstances attempt to g...

Страница 6: ...e is harmful to skin and eyes It is toxic CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries...

Страница 7: ...ctions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC v...

Страница 8: ...nuously conditions and regu lates its output voltage whether utility power is present or not It supplies connected equipment with clean sinewave power Sensitive electronic equipment operates best from...

Страница 9: ...e amount of distortion reflected on the utility is reduced This results in cleaner power being available to other devices in the building not being protected by the GXT2 6000RTL630 2 3 Inverter In nor...

Страница 10: ...external battery cabinets are available to extend battery run times 2 7 Dynamic Bypass The GXT2 6000RTL630 provides an alternate path for utility power to the connected load in the unlikely event of a...

Страница 11: ...eries to lighten the UPS for easier installation The internal batteries may be installed after the cabinet has been placed in its final floor or rack position The Power Distribution box is shipped sep...

Страница 12: ...OUTPUT BREAKER 20A 240V T ON ON INPPUT OUTPUT ONLY CB DOES NOT CONNECT BYPASS POWER TO MANUAL BYPASS SWITCH BREAKER 30A ON OFF OFF OFF UPS UTILITY COMMUNICATION PORT SEE MANUAL FOR CONNECTIONS OFF RE...

Страница 13: ...andard box for custom installations Figure 4 Optional power distribution PD L630 OUTPUT BREAKER 20A 240V T OUTPUT BREAKER 20A 240V T ON ON INPPUT OUTPUT ONLY CB DOES NOT CONNECT BYPASS POWER TO MANUAL...

Страница 14: ...and screws 2 each Support base 2 Mounting hardware Configuration program CD DB 9 port cover GXT2U Configuration Program www liebert com For use with Liebert GXT2U model UPS systems Version 1 6 For Win...

Страница 15: ...ermine the type of installation and follow the appropriate instructions in either 5 1 1 Tower UPS Installation or 5 1 2 Rack Mount UPS Installation 5 1 1 Tower UPS Installation When using the GXT2 600...

Страница 16: ...ing brackets Part RMKIT18 32 feature retaining latches to prevent users from inadvertently sliding the UPS or battery cabinet out of the rack To install the rack mount brackets 1 Unpack two 2 rack mou...

Страница 17: ...eck alignment of bracket assemblies and TIGHTEN ALL SCREWS FROM Steps 2 and 3 5 Prepare the UPS or battery cabinet the equipment for rack mounting by following instructions in the equipment s user man...

Страница 18: ...flange of the front members you can use the four 4 extra M5 screws provided in the kit to secure the equipment Otherwise the equipment should be secured to the front of the rack with four 4 customer s...

Страница 19: ...ed position using two screws The picture on the left shows the connector in the open position as shipped When the UPS is installed remove the two screws to release the connector Plug the connector int...

Страница 20: ...L630 power distribution box OUTPUT BREAKER 20A 240V T OUTPUT BREAKER 20A 240V T ON ON INPPUT OUTPUT ONLY CB DOES NOT CONNECT BYPASS POWER TO MANUAL BYPASS SWITCH BREAKER 30A ON OFF OFF OFF UPS UTILITY...

Страница 21: ...cuit breaker on the rear fixed panel of the UPS disconnect all power between the main cabinet and the distribution box Models equipped with a manual bypass switch pass bypass power directly to the byp...

Страница 22: ...attery cabinet 5 Connect the supplied external battery cabinet cable to the rear of the external battery cabinet then to the rear of the UPS 6 The UPS is now equipped with additional backup battery ru...

Страница 23: ...ker located on the distribution box The green AC Input indicator should illuminate on the UPS front panel 10 Press the On button for 1 second The BYPASS lamp will light for several seconds before the...

Страница 24: ...50 or 60 Hz Set the Low Battery Warning alarm time from 2 to 30 minutes Enable Disable the Auto Battery test Set the Auto Battery test to 7 14 21 or 28 days Specify the number of external battery cab...

Страница 25: ...LEDs illuminate allow the UPS to recharge the batteries for 24 hours After 24 hours retest the batteries After the batteries have been retested if only three of the five Battery LEDs illuminate conta...

Страница 26: ...MultiLink 3 x software and can remotely initiate the battery test 8 5 Fault Indicator LED Red The Fault indicator LED is illuminated if the UPS has detected a problem Also one or more of the battery l...

Страница 27: ...el indicator represents a 20 capac ity level As capacity decreases fewer indicators remain illumi nated Refer to 12 0 Troubleshooting For approximate battery run times refer to Table 5 These times are...

Страница 28: ...gnal will start a 2 minute shutdown timer The timer cannot be stopped After 2 minutes the UPS will shut down 4 If utility power returns during the 2 minute timer countdown the shutdown timer will cont...

Страница 29: ...license Kits visit our Web site www liebert com or contact your local dealer or Liebert representative Several option cards are available for use in the Intellislot port of the GXT2 6000RTL630 The Int...

Страница 30: ...ment to comply with national and local wiring codes and regulations REPO switch connection diagram CAUTION To maintain safety SELV barriers and electromagnetic compatibility signal cables should be se...

Страница 31: ...length of time it is essential to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries Failure to recharge the batteries peri odically will result in...

Страница 32: ...way 8 Reconnect the electrical connections for each battery pack 9 Install the battery retaining brackets using the Phillips removed earlier 10 Install the battery access panel and tighten the captive...

Страница 33: ...t breaker on the rear of the UPS 7 Remove the distribution box from the UPS a Loosen all three captive screws until the box releases b Pull box away from the UPS and set the box aside on a padded surf...

Страница 34: ...ainst the UPS and tighten the captive screws Do not overtighten 6 If the utility branch circuit breaker and load is off turn the branch breaker on now 7 Turn on the output circuit breaker on the rear...

Страница 35: ...Please have the UPS model number and serial number available at the time of your inquiry Table 2 Indicator meanings LED status Diagnosis Audible alarm All LEDs On bypass due to output overload beep e...

Страница 36: ...ive or the Liebert Worldwide Support Group Fault and Bypass indicator LEDs and diagnostic LED B are illuminated UPS internal DC bus overvoltage UPS requires service Contact your local dealer Liebert r...

Страница 37: ...utility failure One short beep every 10 seconds more than 2 minutes of run time remaining Low Battery Two short beeps every 5 seconds less than 2 minutes of run time remaining Output Overload Bypass...

Страница 38: ...s 10 94 20 46 30 29 40 21 50 17 60 13 70 11 80 9 90 8 100 7 Internal Battery 1 External Battery Cabinet minutes 10 222 20 124 30 81 40 60 50 49 60 39 70 33 80 28 90 24 100 21 Internal Battery 2 Extern...

Страница 39: ...s The UPS will update the anticipated run time calculation only under certain conditions The UPS must have a steady load that is greater than 20 The UPS must be at 100 charge at the start of a battery...

Страница 40: ...Nominal Waveform Sinewave Main Mode Overload 200 for 96 milliseconds 131 199 for 2 seconds 112 129 for 10 seconds with transfer to bypass Bypass Protection Limits Disable Bypass operation If input vo...

Страница 41: ...W 28 12FT Electrical Characteristics Back up Time See Table 5 Battery run times Recharge Time 3 hrs to 90 capacity after full discharge into 100 load Table 8 Output distribution specifications Model N...

Страница 42: ...tery Parameters Type Valve regulated non spillable flame retardant lead acid Qty x V 20 x 12V Battery Manufacturer Part Yuasa REW 45 12 Backup Time See Table 5 Battery run times Environmental Operatin...

Страница 43: ......

Страница 44: ...bert Corporation All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring 800 222 5877 monitoring emersonn...

Отзывы: