Maintenance
27
11.0 M
AINTENANCE
11.1 Internal Battery
The GXT2-6000RTL630 requires very little maintenance. The batteries are valve-regulated, non-
spillable, flame retardant, lead acid, and should be kept charged to obtain their designed life. The
UPS continuously charges the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours
every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri-
odically will result in permanent degradation of battery capacity.
The GXT2-6000RTL630 is designed to allow the user to safely replace the internal batteries. Read the
safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the
appropriate replacement battery kit part number and pricing.
!