Liberty Pumps SBX Series Скачать руководство пользователя страница 4

 

©Copyright 2012 Liberty Pumps Inc.    All rights reserved                                                             4 

 

Fig. 2 Cutting the Inlet Hubs 

wish to use.  Cut 1/4” (but not more than 3/4”) of material from those inlet hubs to assure a good drain tile fit (see fig. 2).  Insert the 

drain tile into the cut inlet hub.  Allow about 1” of spacing between the end of the drain tile and the internal strainer basket for good 

operation and easy removal of the strainer during maintenance (see fig. 3).

 

D. 

Final Backfill.  

Large rocks, clods, and foreign objects should be kept out of the backfill material.  Only fine, 1/4" to 3/4" pea gravel, 

or 1/8" to 1/2" washed, crushed stone is recommended.  Do not use sand or native soil as backfill.  Provide access to the basin 

cover for maintenance and service.

 

IMPORTANT: Do not exert heavy pressure or run heavy equipment on the backfill as this could cause damage to the tank. 

 

 

 

 

 

 

 

Finish Plumbing and Alarm Installation 

IMPORTANT:  All  plumbing  installations  (waste  and  vent)  should  done  by  a  qualified  professional  and  in  accordance  with 

applicable codes.

  

A.  Remove and recycle the disposable protective cover before plumbing the system. 

B. 

NOTE: Threaded connections at cover - HAND TIGHTEN ONLY and use Teflon tape as a thread sealant.  

Remove the gray 

plug and

 

install 1-1/2” PVC pipe to the cover connection labeled “1-1/2” DISCHARGE” (see figure 4).  A union should be installed 

to facilitate pump removal if necessary.  A free-flow swing check valve is recommended after the union to prevent the backflow of 

liquid after each pumping cycle.  A gate or ball valve should follow the check valve to allow periodic cleaning of the check valve or 

removal of the pump.  The remainder of  the discharge line should be as short as possible with a minimum number of turns, to 

minimize friction head loss.  Contact Liberty Pumps or other qualified person if you have questions regarding proper pipe sizes and 

flow rates. 

C.  If your system is equipped with an alarm, refer to the alarm Installation Instructions for proper connection.  The alarm box and 

accessories are located under the clear protective cover.  The alarm switch cord has bare wire leads and exits the cover through 

the single hole grommet (see fig. 4).

 

 

 

 
 

 

 

 

 

 

 

Fig. 3 Drain Tile Placement 

Содержание SBX Series

Страница 1: ...e Tree Avenue Bergen NY 14416 Phone 800 543 2550 Fax 585 494 1839 www libertypumps com Contents 1 General Information 2 Precautions Pre installation 3 Installation 4 Operation and Maintenance 5 Troubl...

Страница 2: ...and amperage requirements of the motor as noted on the pump nameplate The electrical outlet or panel shall be within the length limitations of the pump power cord and at least 4 feet above floor level...

Страница 3: ...per ground has been established A UL listed circuit analyzer will indicate if the power neutral and ground wire are properly connected 8 A qualified licensed electrician should install and test all el...

Страница 4: ...with applicable codes A Remove and recycle the disposable protective cover before plumbing the system B NOTE Threaded connections at cover HAND TIGHTEN ONLY and use Teflon tape as a thread sealant Rem...

Страница 5: ...rovided on the cover to properly center the drill see figure 4 above Install the provided 3 pipe seal in the hole Place 3 PVC vent pipe from the vent system through the pipe seal Do not place the vent...

Страница 6: ...cover Lift up on the two handles see fig 8 and remove the strainer basket Caution water will continue to drip from strainer after removal Clean the basket by dumping the debris and rinsing Reinstall...

Страница 7: ...ing for proper connections and adequate voltage and capacity Switch is unable to move to the turn on position due to interference with the side of basin or other obstruction Position the pump or switc...

Страница 8: ...n or transportation There is no other express warranty All implied warranties including those of merchantability and fitness for a particular purpose are limited to three years from the date of purcha...

Страница 9: ...P 115V SBX280A 1 2HP 115V Alarma ALM 2 IMPORTANTE cuando est instalando la unidad aseg rese de dejar suficiente espacio para acceder a las cubiertas del sistema y poder prestar servicio al tamiz inter...

Страница 10: ...metros 4 pies como m nimo por encima del piso para evitar problemas en caso de inundaci n Se deber instalar la unidad seg n las disposiciones del c digo el ctrico nacional NEC de Estados Unidos y tod...

Страница 11: ...nes del NEC 7 Compruebe que todos los tomacorrientes est n conectados a tierra Se puede usar un analizador de circuitos con aprobaci n UL para verificar que la energ a el neutro y el hilo de masa est...

Страница 12: ...as de residuos y de ventilaci n deben ser instaladas por un profesional calificado y conforme a los c digos aplicables A Quite la tapa desechable de protecci n y rec clela antes de empezar a montar la...

Страница 13: ...para que la junta obturadora no permita el paso de gases vea la figura 5 Las juntas obturadoras deben crear un sello entre las tapas B Instale una l nea de ventilaci n de 7 62 cm 3 plg en el punto de...

Страница 14: ...o Agarre las dos asas figura 8 y saque el tamiz Tenga cuidado ya que seguir goteando agua del tamiz cuando lo haya retirado Vac e la suciedad que haya en el tamiz y enju guelo Vuelva a instalarlo tan...

Страница 15: ...le o el flujo el ctrico se ha visto interrumpido de alg n otro modo tensi n incorrecta Compruebe que la bomba est enchufada Haga que un electricista compruebe que todos los cables est n correctamente...

Страница 16: ...citas incluidas las de comerciabilidad y adecuaci n para un prop sito determinado est n limitadas a un plazo de tres a os a partir de la fecha de compra Esta garant a representa el nico remedio del co...

Страница 17: ...0 1 2 HP 115 V SBX280A 1 2HP 115 V ALM 2 Alarme IMPORTANT Afin de permettre l entretien du filtre de l interrupteur et de la pompe s assurer de permettre un acc s facile aux couvercles protecteurs du...

Страница 18: ...e de la pompe La prise lectrique ou le panneau doit se trouver la port e du cordon d alimentation de la pompe et au moins 1 2 m 4 pi au dessus du niveau du plancher pour minimiser les dangers possible...

Страница 19: ...rer que la mise la terre fonctionne bien Un multim tre approuv par UL indiquera si les fils sous tension neutres et de mise la terre sont raccord s correctement 8 Un lectricien autoris qualifi doit in...

Страница 20: ...igueur A Retirer et recycler le couvercle de protection jetable avant de raccorder la plomberie du syst me B REMARQUE Raccordements filet s au couvercle RESSERRER LA MAIN SEULEMENT et utiliser du ruba...

Страница 21: ...Installer l anneau d tanch it de 3 po pour tuyau dans l orifice Installer un tuyau d vent de 3 po dans l orifice de ventilation travers l anneau d tanch it pour tuyau Ne pas ins rer le tuyau d vent pl...

Страница 22: ...t retirer le couvercle d acc s Soulever le deux poign es voir fig 8 et retirer le panier filtrant Mise en garde de l eau va continuer d goutter du panier apr s son retrait Nettoyer le panier en jetant...

Страница 23: ...uer des r glages Probl me Cause Mesure correctrice La pompe ne fonctionne pas Fusible br l ou autre interruption d alimentation tension inad quate S assurer que le branchement de l appareil est s curi...

Страница 24: ...it marchande et d aptitude une fin particuli re est limit e trois ans partir de la date d achat Cette garantie contient le recours exclusif de l acheteur et exclut lorsque permis par la loi toute resp...

Отзывы: