Liberty Pumps LGH02 Series Скачать руководство пользователя страница 8

8 | EN

Copyright © Liberty Pumps, Inc. 2022 All rights reserved.

5595000B

 Starting System

1.

Double check all wire connections.

2.

Turn pump(s) to OFF position on H-O-A switch.

3.

Turn on breakers.

4.

Test each pump separately in Hand mode and observe 

operation. If 3-phase pump is noisy or vibrates, rotation is 

wrong. Refer to 

3-Phase Pump Rotation Verification

.

5.

Set H-O-A switch(es) to AUTO position and allow water to rise 

in basin until one pump starts. Allow pump to operate until 

the level drops to turn-off point.

6.

Allow basin level to rise to start other pump(s). Notice run 

lights in panel. Pumps should alternate on each successive 

cycle of operation.

7.

Turn H-O-A switch(es) to OFF position and allow basin to fill 

to the override (alarm) control level(s). 

8.

Observe all floats in operation to verify that there is adequate 

clearance to the surrounds to ensure that the floats do not 

have the opportunity to get hung up in their travel. 

9.

Verify alarm system response.

10.

Turn switch(es) to AUTO position; pumps should start and 

operate together until level drops to turn-off point.

11.

Repeat this operation and cycle several times before leaving 

the site.

12.

Check voltage when pumps are operating and record the 

amp draw of each pump. Check amps on each wire as 

sometimes a high leg will exist. For excessive voltage on one 

leg, the electric utility company shall be consulted.

13.

Complete Startup Report.

Be certain to complete adequate testing, especially on systems 

with multiple pumps or custom control configurations.

Ma intena nce  a nd  Troubleshooting

Accidental contact with electrically live parts, items, fluid, or 

water can cause serious injury or death.

Always disconnect pump(s) from power source(s) before 

handling or making any adjustments to either the pump(s), 

the pump system, or the control panel.

Wear adequate Personal Protective Equipment when working 

on pumps or piping that have been exposed to wastewater. 

Sump and sewage pumps often handle materials that can 

transmit illness or disease upon contact with skin and other 

tissues.

Do not enter a pump basin after it has been used. Sewage and 

effluent can emit several gases that are poisonous.

Verify correct 3-phase pump rotation before returning to 

service.

 Maintenance

As the motor is oil-filled, no lubrication or other maintenance is 

required.
To keep the pump/pump system operating smoothly, perform the 

following routine checks. Severe operating environments will 

require more frequent checks. For any issues that are not 

resolvable, contact Liberty Pumps for further assistance.

 Monthly 

1.

Pumps that are idle for more than a month in a dry basin 

should have impellers manually operated through the breaker 

panel monthly to lubricate the seals. 

Limit the lubrication run 

time to less than one minute per pump.

2.

Pumps that are idle in a wet basin must be removed—

do not 

store pump in wet basin.

 Quarterly 

1.

Check pumps for corrosion and wear.

2.

Check for free and unobstructed float switch operation and 

float switch condition.

3.

Inspect for proper check valve operation.

4.

For multiple pumps, check for balanced operating times. 

Uneven times indicate a defective unit, float switch or control.

5.

Inspect the control panel for any presence of moisture in 

enclosure, loose connections, and general component 

condition.

 Annually 

1.

Basin should be inspected and cleaned. Replace any defective 

components.

 Troubleshooting

Refer to Table

 

for troubleshooting guidance.

No repair work shall be carried out during the warranty period 

without prior factory approval. To do so may void the warranty.
Liberty Pumps, Inc. assumes no responsibility for damage or injury 

due to disassembly in the field. Disassembly, other than an 

authorized motor enclosure repair facility approved by Liberty 

Pumps or its authorized service centers, automatically voids 

warranty.

RISK OF ELECTRIC SHOCK

RISK OF SERIOUS INJURY OR DEATH

Содержание LGH02 Series

Страница 1: ...y as possible on all installations to protect from system pressures Installer manual must remain with owner or system operator maintainer Record information from pump nameplate Model Serial Control Pa...

Страница 2: ...wer cord This will damage the power cord and could expose the electrically live wires inside the power cord The electrical power supply shall be located within the length limitations of the pump power...

Страница 3: ...Proper venting of sewer and effluent gases alleviates poisonous gas buildup and reduces the risk of explosion and fire from these flammable gases Wear adequate Personal Protective Equipment when worki...

Страница 4: ...s will be according to the control selected see separate operation instructions supplied with the unit IMPORTANT When connecting an LEP Series pump to an existing control panel verify the panel is cor...

Страница 5: ...higher than the full load input power indicated on the pump nameplate Power and Control Cords Do not remove cord and strain relief and do not connect conduit to pump The power and control cords are fi...

Страница 6: ...that the cutter and impeller are freely spinning rotating the cutter helps to lubricate the shaft seals if the pump has been non operational for more than a week It is recommended to rotate the cutter...

Страница 7: ...200 PSI service See Liberty Pumps line of CSV Series Curb Stop Swing Check Valve Assemblies and CK Series Connection Kit Vent The fiberglass basin provided with the system must be completely sealed an...

Страница 8: ...ive Equipment when working on pumps or piping that have been exposed to wastewater Sump and sewage pumps often handle materials that can transmit illness or disease upon contact with skin and other ti...

Страница 9: ...valve partially closed or clogged Check the discharge line for foreign material including ice if the discharge line passes through or into cold areas Check valve partially clogged Raise liquid level...

Страница 10: ...heck valve Repeated tripping Circuit protection underrated Check rating and replace with proper size Current unbalance Check current draw Other appliance on same circuit Pump requires separate circuit...

Страница 11: ...the discharge line passes through or into cold areas Check valve is stuck closed or installed backward Remove check valve s and examine for freedom of operation and proper installation Gate or ball va...

Страница 12: ...der this Warranty if the product has not been properly installed or maintained in accordance with the printed instructions provided if it has been disassembled modified abused or tampered with if the...

Отзывы: