Pump operates noisily.

Piping attachments to building are too rigid.

Replace a portion of the discharge line with 

rubber hose or connector.

Incorrect motor rotation.

1-phase: verify capacitor wiring in Figure

 

1, else 

consult factory.

3-phase: correct pump rotation direction. Refer 

to section 

3-Phase Pump Rotation 

Verification

.

Pump is being run below minimum head 

requirement causing cavitation.

A different sized pump or impeller may be 

required. Consult Liberty Pumps.

Foreign objects in the impeller cavity.

Clean the impeller cavity.

Broken impeller.

Consult Liberty Pumps for information 

regarding impeller replacement.

Worn bearings.

Return pump to an authorized repair facility.

Pump runs or hums but does not 

pump.

Discharge line blocked or restricted.

Check the discharge line for foreign material, 

including ice if the discharge line passes 

through or into cold areas.

Check valve is stuck closed or installed 

backward.

Remove check valve(s) and examine for freedom 

of operation and proper installation.

Gate or ball valve is closed.

Open gate or ball valve.

Total head is beyond pump's capability.

Route piping to a lower level. If not possible, a 

larger pump may be required. Consult Liberty 

Pumps.

Obstructed impeller or volute.

Remove obstruction.

Pump is airlocked.

Turn pump off and let set for several minutes, 

then restart.
Add baffle to reduce trapped air bubbles.

Capacitor failure in control panel.

Check capacitors and replace if needed.

Stuck/defective motor contactor in control 

panel.

Replace motor contactor.

Pump is not seated correctly in guide rail base.

Lift pump and re-position.

High level alarm triggering.

Missing or faulty curb stop/swing check valve 

allowing system pressure to feed back through 

discharge piping.

Verify presence of a curb stop check valve or 

replace curb stop/swing check valve assembly.

Table 2. Troubleshooting Matrix (continued)

Problem

Possible Cause

Corrective Action

Содержание LGH02 Series

Страница 1: ...y as possible on all installations to protect from system pressures Installer manual must remain with owner or system operator maintainer Record information from pump nameplate Model Serial Control Pa...

Страница 2: ...wer cord This will damage the power cord and could expose the electrically live wires inside the power cord The electrical power supply shall be located within the length limitations of the pump power...

Страница 3: ...Proper venting of sewer and effluent gases alleviates poisonous gas buildup and reduces the risk of explosion and fire from these flammable gases Wear adequate Personal Protective Equipment when worki...

Страница 4: ...s will be according to the control selected see separate operation instructions supplied with the unit IMPORTANT When connecting an LEP Series pump to an existing control panel verify the panel is cor...

Страница 5: ...higher than the full load input power indicated on the pump nameplate Power and Control Cords Do not remove cord and strain relief and do not connect conduit to pump The power and control cords are fi...

Страница 6: ...that the cutter and impeller are freely spinning rotating the cutter helps to lubricate the shaft seals if the pump has been non operational for more than a week It is recommended to rotate the cutter...

Страница 7: ...200 PSI service See Liberty Pumps line of CSV Series Curb Stop Swing Check Valve Assemblies and CK Series Connection Kit Vent The fiberglass basin provided with the system must be completely sealed an...

Страница 8: ...ive Equipment when working on pumps or piping that have been exposed to wastewater Sump and sewage pumps often handle materials that can transmit illness or disease upon contact with skin and other ti...

Страница 9: ...valve partially closed or clogged Check the discharge line for foreign material including ice if the discharge line passes through or into cold areas Check valve partially clogged Raise liquid level...

Страница 10: ...heck valve Repeated tripping Circuit protection underrated Check rating and replace with proper size Current unbalance Check current draw Other appliance on same circuit Pump requires separate circuit...

Страница 11: ...the discharge line passes through or into cold areas Check valve is stuck closed or installed backward Remove check valve s and examine for freedom of operation and proper installation Gate or ball va...

Страница 12: ...der this Warranty if the product has not been properly installed or maintained in accordance with the printed instructions provided if it has been disassembled modified abused or tampered with if the...

Отзывы: