How to set Interface unit
How to set Interface unit
ON
L1 2 3 4
KSDO4H
ON KSDO 4H
ON KSDO4H
ON KSDO4H
ON KSDO4H
ON KSDO4H
ON KSDO4H
P1485(M) DIP Switch Configuration
Select Air
Conditioner Type
Select Network
Type
* LGAP : LG Air conditioner Protocol
1 ON, All others OFF
: Multi V products(Except CRUN products) or
Multi(Non-Inverter) Product applied Common PCB(Refer to
NOTE) or Multi(Inverter) P Central Controller(All
types) - Without LGAP
1 and 4 ON, All others OFF
: Multi V products(Except CRUN products)
or Multi(Non-Inverter) Product applied Common PCB or
Multi(Inverter) P Central Controller(All types) -
Using LGAP
2 ON, All others OFF
: Multi(Non-Inverter) Product
+ Centroller(All types) - Without LGAP
2 and 4 ON, All others OFF
: Multi Non-Inverter Product
+ Central Controller(All Types) - Using LGAP
1,2,3,4 ON
: Multi V CRUN Product
+ Central Controller(All types) - Using LGAP
Multi V & Multi(LGAP applied) products Configuration Methods
CAUTION:
The wrong setting of air-conditioner switch could cause malfunctioning.
Switch setting must be done carefully.
Push the Reset button after changing the Dip switch.
NOTE:
Multi(Non-Inverter) Product applied Common PCB
PCB P/NO. : 6871A20917*
P/NO. : 6871A20918*
P/NO. : 6871A20910*
*Note : LGAP is special protocol using on LG Air-conditioner for central control.