118
Installin
g
ACP
ENGLISH
Run LG ACCS of the ACP to select all indoor units, and execute lock all function.
Afterwards, execute temperature lock function again, and monitor the status of the ACP.
Check the status of the ACP according to the following flowchart.
ACP status monitoring after executing lock all and temperature lock
After selecting all indoor units,
execute lock all and temperature
lock
When you set the system in ACP or
AC Manager, temperature lock
(individual lock) is unlocked, so execute
temperature lock (individual lock) again.
Are lock all
released in some
indoor units?
Are lock all
released in some
indoor units?
Insert 2PIN connector into PI485.
Check outdoor unit S/W version
through MV and perform
on-boarding (upgrade) of the
program to Version34 or higher.
Carry out on-boarding of PI485
software or check the number to
replace with product with the
function.
Check if the indoor unit power is
shut down. If indoor unit is reset,
lock all will be released, so execute
lock all again.
Is the
temperature lock
unlocked?
No
No
Yes
Yes
Yes