6
INSTALLATION OF OUTDOOR UNIT
ENGLISH
More than
300mm
Fence
or
obstacles
Sunroof
More than
More than
300mm
300mm
More than
300mm
More than
600mm
More than
700mm
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
If installed tube is shorter than 7.5 m, additional charging is not necessary.
Additional Refrigerant = (A -7.5) x Additional refrigerant (g)
Model
Pipe Size mm(inch)
Length A(m)
Elevation B(m)
Additional
refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
UU12WH
Φ
9.52(3/8)
Φ
6.35(1/4)
5
30
5
20
20
UU18WH
Φ
12.7(1/2)
Φ
6.35(1/4)
5
50
5
30
20
UU21WH
UU24WH
Φ
15.88(5/8)
Φ
9.52(3/8)
5
50
5
30
40
UU24WH
Ø15.88
(5/8)
Ø9.52
(3/8)
5
50
5
30
40
UU36WH
UU42WH
UU48WH
Ø15.88
(5/8)
Ø9.52
(3/8)
5
75
5
30
40
Piping length and the elevation
Single Operation
Outdoor unit
- If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure
that heat radiation from the condenser is not
restricted.
- Ensure that the spaces indicated by arrows
around front, back and side of the unit.
- Do not place animals and plants in the path
of the warm air.
- Take the air conditioner weight into account
and select a place where noise and vibration
are minimum.
- Select a place so that the warm air and noise
from the air conditioner do not disturb neigh-
bors.
INSTALLATION PLACES
More than
300mm
More than 700mm
More than 600mm
OUTD
OOR
OU
TD
OO
R
Unit
Unit
More than
More than
300mm
300mm
OUTD
OOR
OU
TD
OO
R
Unit
Unit
OUTD
OOR
Unit
Sunroof
More than
300mm
Fence or
obstacles