34
EXTERNAL STATIC PRESSURE
ENGLISH
EXTERNAL STATIC PRESSURE
* Only for ceiling concealed duct type
Capacity
(kBtu/h)
Step CMM
Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29)
4(39)
6(59)
8(78) 10(98) 12(118) 13(127) 14(137) 15(147)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
24
LOW
14.5
76
77
85
89
97
106
114
121
124
127
132
MID
16.5
85
87
90
94
103
111
118
125
128
131
136
HIGH
18
90
92
95
99
108
115
122
129
132
135
138
Capacity
(kBtu/h)
Step CMM
Static Pressure[mmAq(Pa)]
4(39)
5(49)
6(59)
7(69)
8(78)
9(88) 10(98) 11(108) 12(118) 13(127) 15(147)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
36
LOW
24
88
91
95
100
101
108
113
115
118
121
128
MID
28
93
97
101
105
108
115
118
120
124
127
134
HIGH
32
101
105
109
112
115
119
123
126
128
133
137
NOTE
!
1. Be sure to set the value refering table 2. Unexpected set value will cause mal-function.
2. Table 2 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
* If it is zero static pressure, please set value below Maximum value.
Capacity (kBtu/h)
Maximum value
24
115
36
120
Capacity (kBtu/h)
Factory set (E.S.P.) mmAq(Pa)
24
6(59)
36
Содержание UBN24R