INSTALLATION OF INDOOR UNIT
ENGLISH
Point for attention regarding quality of the public electric power supply
This equipment complies with respectively:
- EN/IEC 61000-3-12 (1) provided that the short-circuit power Ssc is greater than or equal to the
minimum Ssc value at the interface point between the user's supply and the public system. It is
the responsibility of the installer or user of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the equipment is connected only to a supply
with respectively: Ssc greater than or equal to the minimum Ssc value.
- European/International Technical Standard setting the limits for voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current
≤
75 A.
- European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current
≤
16 A of > 75 A per
phase.
Circuit Breaker Specification
Perform the electrical wiring work according
to the electrical wiring connection.
- All wiring must comply with local
requirements.
- Select a power source that is capable of
supplying the current required by the air
conditioner.
- Use a recognized ELCB(Electric Leakage
Circuit Breaker) between the power source
and the unit. A disconnection device to
adequately disconnect all supply lines must be fitted.
- Model of circuit breaker recommended by authorized personnel only
- Select a circuit breaker rating appropriate for the maximum running current.
Model Name
Minimum Ssc Value
Phase
(Ø)
Capacity
(kW)
1
5
3 142
7
9
12
14
16
Model Name
Minimum Ssc Value
Phase
(Ø)
Capacity
(kW)
3
12
2 348
14
16
ELCB
CB
Outdoor Unit
Indoor
Unit
Power Source
Communication
Switch Box
Type
Refrigerant
Capacity (kW)
Phase (Ø)
Maximum Running
Current (A)
1)
Current
(Max.) [A]
2)
Split
R410A
5 / 7 / 9
1
23.0
19.0
12 / 14 / 16
1
35.0
42.0
12 / 14 / 16
3
15.0
16.1
R32
5 / 7 / 9
1
23.0
27.6
Hydrosplit
R32
12 / 14 / 16
1
33.0 / 34.0 / 35.0
42.0
12 / 14 / 16
3
12.0 / 12.5 / 13.0
16.1
1) Maximum running current is the maximum current value maintained during the operation of
the unit.
2) Current(Max.) is the maximum current value when a compressor of unit is off.