137
CONFIGURATION
ENGLISH
Outdoor PCB (12, 14, 16 kW)
OFF is selected
ON is selected
OFF
ON
SW2
1 2 3 4 5 6
Description
Description
Setting
Setting
Default
Default
Peak Control
Low Noise Mode
3
3
Max Mode
2
Limited Low Noise Mode
2
Normal Low Noise Mode
Peak Control : To limit maximum
current (Power saving)
3
2
DIP Switch Information
h
Only DIP-switch no. 2 and no.3 has a function. Others have no function.
h
When setting the limited low noise mode, Mode can be exited to secure capacity after
operating for a certain time.
NOTE
* Input current value can be limited by DIP Switch operation.
Capacity
Mode
Max Mode
Running Current(A)
Peak Control Mode
Running Current(A)
1Ø 5,7,9 kW
Cooling
23
17
Heating
23
17
1Ø 12,14,16 kW
Cooling
35
25
Heating
35
27
3Ø 12,14,16 kW
Cooling
15
10
Heating
15
12