51
INSTALLATION
ENGLISH
Point for attention regarding quality of the public electric power supply (For
4 Series)
- European/International Technical Standard setting the limits for voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current
≤
75 A.
- European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current
≤
16 A of > 75 A per
phase.
For 1 Phase (12, 14, 16 kW)
- This equipment complies with IEC (EN) 61000-3-12 in harmonic currents emission limits
corresponding Rsce = 33.
- This equipment complies with reference impedance for IEC (EN) 61000-3-11.
For 3 Phase (12, 14, 16 kW)
- This equipment complies with IEC (EN) 61000-3-12 provided that the short-circuit power Ssc is
greater than or equal to 2672 kVA at the interface point between the user’s supply and the public
system. It is the responsibility of the installer or user of the equipment to ensure, by consultation
with the distribution network operator if necessary, that the equipment is connected only to a
supply with a short-circuit power Ssc greater than or equal to 2672 kVA.
- This equipment complies with IEC (EN) 61000-3-3.
For 1 Phase (5,7 kW)
- This equipment complies with IEC (EN) 61000-3-2.
- This equipment complies with IEC (EN) 61000-3-3.
For 1 Phase (9 kW)
- This equipment complies with IEC (EN) 61000-3-12 in harmonic currents emission limits
corresponding Rsce = 33.
- This equipment complies with IEC (EN) 61000-3-3.