INSTALLER SETTING
ENGLISH
Hysteresis Room Air(Cooling)
It is a function to adjust the cooling air temperature Thermal On / Off temperature according to
the field environment in order to offer optimized cooling operation.
• In the Installer setting list, and select Hysteresis Room Air(Cooling) setting category, and press
[OK] button to move to the detail screen.
Value
Default
Range
Temp On
0.5 °C
0 ~ 3 °C
Temp Off
-0.5 °C
-3 ~ 0 °C
Current Temp.
Type0 (TH On)
Type0 (TH Off)
Target Temp.
Thermal
On
Thermal
Off
Thermal
On
Thermal
Off
Comp
On
Comp
Off
Comp
On
Comp
Off
- Example : Type0 setting
OK