- 92 -
73
AC input instant over
current error
(Matter of software)
PCB(Inverter) input
power current is over
48A(peak) for 2ms
1. Overload operation (Pipe clogging/Covering/EEV
defect/Ref.overcharge)
2. Compressor damage
(Insulation damage/Motor damage)
3. Input voltage abnormal (L, N)
4. Power line assemble condition abnormal
5. PCB assembly 1 damage
(input current sensing part)
Display
code
Title
Cause of error
Check point & Normal condition
n
Error Diagnosis and Countermeasure Flow Chart
No
1.Check Pipe clogging/distortion
2.Check Covering (Unit)
3.Check EEV connector assemble condition/normal operation
4.Check refrigerant pressure
→
Reassemble or manage if abnormality found
Is installation
condition normal?
Is compressor
Wire connection
condition normal?
1.Check PCB assembly 1 U,V,W connector connection condition
2.Check wire disconnection and wiring
3.Check compressor terminal connection condition(bad contact)
→
Reassemble if abnormality found
Is AC input Wire connection
condition normal?
1.Check R,S,T connection condition
2.Check wire disconnection and wiring
→
Reassemble if abnormality found
PCB assembly 1
normal?
Yes
No
Recheck power and
installation condition
Yes
Yes
Yes
No
No
Yes
No
Check
R-S, S-T, T-R phase voltage is 220~240 V ± 10%
→
Check connection condition and wiring if power is abnormal
Is input voltage normal?
Check PCB assembly 1 IPM normality
→
Replace PCB assembly 1
Содержание THERMA V AHBW076A0
Страница 7: ... 7 Part 1 General Information 1 Model Names 8 2 External Appearance 8 3 Nomenclature 9 ...
Страница 13: ... 13 Part 2 Features Controls 1 List of Function 11 2 Features Controls 12 3 Test Run 34 ...
Страница 46: ... 46 Part 5 Trouble Shooting ...
Страница 74: ... 74 Vdc AHBW126A0 AHBW146A0 AHBW166A0 P GND ...
Страница 86: ... 86 AHBW126A0 AHBW146A0 AHBW166A0 EEPROM ...
Страница 98: ...P NO MFL68026801 October 2013 ...