- 62 -
14 Problem in Flow Switch
Code
No.
Description
Cause
Normal Condition
• Flow switch is open while in-
ternal water pump is working
• Flow switch is closed while inter-
nal water pump is not working
• Flow switch is open while DIP
switch No. 5 of main
PCB(Heater) is set as ON
• Flow switch should be closed while inter-
nal water pump is working or DIP switch
No. 5 of main PCB(Heater) is set as ON
• Flow switch should be open while in-
ternal water pump is not working
n
Error diagnosis and countermeasure flow chart
Start
The flow switch is
electrically open.
END
(it is normal
condition)
The water pump
is in trouble.
Water is not enough
or there can be
water leakage inside
water circuit.
The flow switch is
electrically closed.
A
B
C
D
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
YES
NO
System stopped
while operation
Water pump
still running
(*)
Water pump
running
(*)
Control Panel
Shows ‘CH14’
Control Panel
Shows ‘CH14’
Pressure gauge
indicates 150~200 kPa
(*): How to identify? - Touch the terminal box (black plastic box at
the water pump) of water pump and feel if the water pump is vi-
brating. If no vibration, the water pump is not operating. Also, you
can see ‘Water Pump Operating Icon ( )’ at control panel.
• Although there is not water flow inside water circuit, the flow switch detects as if water is flowing. It is
due to electrically closed (or short) of flow switch or the contact of flow switch is mechanically stuck.
• Contact official After Service Center and replace the flow switch.
• Check the air vent. If there is air in the unit, it can display “CH14”. Please remove the air by using the air vent.
• Check if water inside water circuit is fully charged. Pressure gauge at the unit should indicate 150~200 kPa.
• Also, as the hand of the pressure gauge is not react so fast according to water charging, check the pressure gauge again.
• Otherwise, there can be water leakage inside water circuit. Examine if water circuit is completely sealed.
• Although water is well flowing, the flow switch can not detect water flow. It is due to electrically open of flow
switch or the contact of flow switch is mechanically broken.
• Contact official After Service Center and replace the flow switch.
• Read ‘Checking Key Components of unit – Water Pump’ carefully to get more detail information.
• Contact official After Service Center and replace the water pump.
• Also, check the water quality if there are particles that can yield locking at the shaft of the water pump.
• Check the air vent. If there is air in the unit, it can display “CH14”. Please remove the air by using the air vent.
A
B
C
D
Содержание THERMA V AHBW076A0
Страница 7: ... 7 Part 1 General Information 1 Model Names 8 2 External Appearance 8 3 Nomenclature 9 ...
Страница 13: ... 13 Part 2 Features Controls 1 List of Function 11 2 Features Controls 12 3 Test Run 34 ...
Страница 46: ... 46 Part 5 Trouble Shooting ...
Страница 74: ... 74 Vdc AHBW126A0 AHBW146A0 AHBW166A0 P GND ...
Страница 86: ... 86 AHBW126A0 AHBW146A0 AHBW166A0 EEPROM ...
Страница 98: ...P NO MFL68026801 October 2013 ...