- 30 -
Code
Item
Detail
Remark
2B
Function
Sanitary water heating timers
Description
Value #1
Note
Default
Range
5 ~ 95 min (step: 5 min)
Value #2
Note
Default
30 min
Range
0 ~ 600 min (step: 30 min)
180 min
Determine following time duration : operation time of sanitary tank
heating, stop time of sanitary tank heating, and delay time of
sanitary tank heater operating.
This time duration defines how long time sanitary tank heating can
be stopped. It is also regarded as time gap between sanitary tank
heating cycle.
Value #3
Note
Default
Range
20 ~ 95 min (step: 5 min)
20 min
This time duration defines how long time sanitary tank heater
will not be turned on in sanitary water heating operation.
This time duration defines how long time sanitary tank heating can
be continued.
2A
Function
Miscellaneous setting
Description
Determine electric heater and water heater on and off
Value #1
Note
00: Operate both electric heater and sanitary tank heater
01: Operate only sanitary tank heater
Default
00
Range
00 ~ 01
Value #2
Note
Not used
Default
-
Range
-
※
Some contents may not be displayed depending on DIP switch setting in the main PCB assembly 2.
Содержание THERMA V AHBW076A0
Страница 7: ... 7 Part 1 General Information 1 Model Names 8 2 External Appearance 8 3 Nomenclature 9 ...
Страница 13: ... 13 Part 2 Features Controls 1 List of Function 11 2 Features Controls 12 3 Test Run 34 ...
Страница 46: ... 46 Part 5 Trouble Shooting ...
Страница 74: ... 74 Vdc AHBW126A0 AHBW146A0 AHBW166A0 P GND ...
Страница 86: ... 86 AHBW126A0 AHBW146A0 AHBW166A0 EEPROM ...
Страница 98: ...P NO MFL68026801 October 2013 ...