Heat Pump Water Heater
-
5
0 Hz (R134a)
14. Installation
2
9
Select the best Location
NOTE
• Installation in a confined space without proper
ventilation will lead to higher power
consumption.
• Auxiliary
drain pan MUST be installed in
compliance with local codes.
Drain pan kits are available from the store
where the water heater purchased, or any
water heater distributor.
Drain pan should not obstruct cold water inlet
or drain valve.
- Select space where has enough space for
periodic servicing. The air filter, covers, and
front panels can be removed to permit
inspection and servicing.
- Take the weight of the water heater into
account and select a place where the floor is
strong enough to support the weight of full
water heater.
- The water heater and water lines should be
protected from freezing and high corrosive
elements. Do not install water heater in
outdoor or unprotected areas.
- Install the water heater close to the area of
greatest heater water demand and the center
of plumbing system. Long un-insulated hot
water lines can waste energy.
- Insufficient air exchange will result in increased
energy consumption level.
- The installation site must be over 1 °C.
Minimum Clearances
Minimum room size:
700 ft
3
0.5ft(15cm)
0.5ft
(15cm)
1.5ft(45cm)
0.5ft
(15cm)
1.5ft(45cm)
1.5ft(45cm)
NOTE
• For future service, a minimum 3 feet clearanc
between any object and the left, right and back
side is recommended.
- Ensure the water heater is horizontal using a
spirit level.
- Keep level parallel in installing the product.
Otherwise, it may cause vibration or water
leakage. It may cause injury or an accident.