Heat Pump Water Heater
-
5
0 Hz (R134a)
11.
Electric Characteristics
R5TT20F-SA
1
/ WH20S.F5
Cool
Heat
R5TT20F-SA
1
/ WH20FS.F5
Unit
Type
Hz
Voltage
Inverter
5
0
2
30
Min :
195
Max : 2
65
15
.1
15
.0
-
-
3.3
43
0.22
Compressor
FM
Model
Indoor Unit
Power
MCA
MOP
MSC
RLA
W
FLA
Voltage Range
Note
1.
Voltage range
Voltage supplied to the unit terminals should be within the minimum and maximum range.
2. Maximum allowable voltage unbalance between phase is 2 %.
3. Select wire spec. based on the larger value of MCA.
4.
RLA is measured during each individual compressor test condition.
5.
OFM is measured as the outdoor unit test condition.
6.
Recommended circuit breaker is ELCB
.
(Earth Leakage Circuit Breaker)
MCA : Minimum Circuit Amperes (A)
MOP : Maximum Rating Over Current Protective Device (A)
MSC : Maximum Starting Current (A)
RLA : Rated Load Amperes (A)
FM : Fan Motor
W : Fan Motor Rated Output (W)
FLA : Full Load Amperes (A)