21
ENGLISH
ELECTRICITY WIRING
Electricity wiring
• When the SA(supply air) is used as an induction motor, electric power is supplied to the motor
through U,V, and W of a drive module.
• Apply a 3-frame leakage current breaker with 3-phase, 3-wire system.
• Select the capacity of a leakage breaker in reference to the standard below, and refer to “Elec-
tric Facility Technology Standard or Korea Power Wire Rule.”
Motor
Capacity
Full load operating
current (A)
Wire thickness
(mm
2
)
Leakage current breaker
(3P ELCB)
Induction
motor
2.2 kW
3.9 A
2.5
Below 10 A, 100 mA 0.1 second
3.7 kW
6.6 A
2.5
Below 15 A, 100 mA 0.1 second
5.5 kW
9.7 A
4.0
Below 24 A, 100 mA 0.1 second
7.5 kW
13.2 A
6.0
Below 38 A, 100 mA 0.1 second
Power source for control kit
Power source for control kit,
single-phase 220 V, 60 H
single-phase 220 V, 60 Hz
Power source for operation motors
Power source for operation motors
3 phases
3 phases
E
sa
oa
ra
<MCC panel
<MCC panel>
<Control Kit
<Control Kit>
<SA Drive Kit
<SA Drive Kit>
r
s
t
r
s
t
Drive
n @
f
cRQa cRQb
l
n
r@s@t@
u@v@w
e@HraI
e@HraI
a
b
Terminal