INSTALLATION PROCESS DIAGRAM
11
ENGLISH
INSTALLATION PROCESS DIAGRAM
• Please, install a product in accordance with the process below.
Since maximum 3 outdoor units can be connect-
ed to one communication module, be careful
not to mix piping temperature sensor connected
to each outdoor unit and communication line
connection.
Be sure to install the temperature/humidity sen-
sors which match the specifications to SA (air
supply)/RA (return air) ducts. (specification: -
40 °C~70 °C, RH 0~95 %, AC 24 V/DC 0~10 V)
It needs to connect control kit and drive kit with
a communication line to operate SA (air sup-
ply)/RA (return air fan motor.
- When a constant speed fan motor is used,
refer to the constant speed fan output port of a
wiring diagram.
When an option sensor is applied, set up HMI in
a way to meet the field condition by an installa-
tion field. (Refer to HMI explanation for set up
details.)
When using capacity control:
Be sure to install “central control PI485’ at the
outdoor unit. After completing a Control Kit
installation, set up outdoor unit addresses serial-
ly starting from 1. Erroneous set up in outdoor
unit addresses could disrupt normal operation.
After all installations are completed, set up the
values required for product operation should be
made through HMI system set up. (Refer to
HMI system set up for detailed information.)
Install a Control Kit
Connect piping temperature
sensors
Connect outdoor unit communi-
cation line
Connect AHU sensor
Connect an inverter drive Kit
Connect electric wires
Set up HMI
Set up a system
Set up outdoor unit address
(when using capacity control)
NOTE
!
Installation process could change depending on the construction field conditions, and,
please, conduct installation work with full understanding on the installation manual.