The protocols provided for linking the outdoor units with Modus are as follows.
- Physical Layer: RS-485 Serial Line
- Mode: MODBUS RTU Mode
- Baud Rate: 9 600
- Parity: None Parity
- 1 Stop Bit
- Applied Function Code
Refer to the Modbu Protocols in Appendix for more information on available protocols.
Function Code
Sub Function
Function Name
Start Address form
Master Device
0x01
None
Read Coil
Register Address-1z
0x02
None
Read Discrete Input
Register Address-10001
0x03
None
Read Holding
Register Address-40001
0x04
None
Read Input
Register Address-30001
0x05
None
Write Single Coil
Register Address-1
0x06
None
Write Single Holding
Register Address-40001
0xF1~FF
Reserved for Exception Code