AHU SENSOR CONNECTION
33
ENGLISH
- Filter Differential Sensor (optional)
-I/O PCB #2
Terminal Block#3
<Inside the Control Kit>
AC 24 V(G)
Ground(G0)
DC 0~10 V(U)
B3
B4
G
Ex: Filter Differential Sensor (voltage type) Connection
Item
Specification
Remark
Filter Differential
Sensor
- Power: AC 24 V
- Output signal: DC 0~10 V
- Range: 0~1 000 Pa
Option
1. For more information on the installation of a filter differential sensor, refer to the Manual
that came with the sensor.
2. Make sure to finish all the sensor wires with a flexible tube.
CAUTION
• Improper wiring of the sensor can damage the Main Controller of the AHU.
Make sure to check for any incorrect wiring before turning the power on.
!