52
ENGLISH
HMI SETTINGS/INSTALLATION
CAUTION
• When the filter differential sensor is not set.
- The Clean Filter Alarm will not be displayed if the Filter Differential Sensor is neither
enabled nor disabled after installation.
!
4) Filter Differential Pressure Setting
- When the filter differential sensor is not used, do not check the checkbox
.
Check the checkbox
only when the sensor is used.
- You'll be able to see the filter differential sensor value in the System View only when the
sensor is enabled by checking the checkbox.
- The Default Concentration Level of the filter differential sensor must be set before the sen-
sor can be used. Set the default filter differential pressure value as shown below.
- The initial value of the default pressure level is set to 400Pa, and the level can be set be-
tween 200~400Pa at an increment/decrement of 10Pa.
- If a value exceeding the default pressure level is entered, a message saying "Exceeded
Maximum Input Range", so re-enter the value within the designated range when you get
this message.
When the filter differential sensor is not used.
When the filter differential sensor is used.
①
To set the default pressure level, click the Default
Pressure Level display to open a screen where the
default pressure level can be entered.
②
Enter the desired input value by using the key
button.
③
Enter the default pressure level value and then
click the 'OK' button to enter the input value.