Setting and using method
Installation Manual
15
ENGLISH
3) Fan level setting mode
4) Power save mode
Ú
When the indoor unit is operating with a Dry contact For Economizer, the fan level can be changed by
other controller when the fan level is set to low level and the indoor is in unlocked condition.
Ú
When setting 9, A mode, the TEMP_SETTING must always be set to ON.
Ú
Power save mode: Adjust the set temperature to +3℃(6℉) for cooling and -3℃(6℉) for heating.
Input A
Input B
Operating mode
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Indoor unit operating at low level, locked
Indoor unit operating at low level, unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
Indoor unit operating at low level, locked
Indoor unit operating at low level, unlocked
Indoor unit stopped, locked
Indoor unit prior operating condition maintained, unlocked
CONTROL
MODE SWITCH
7
8
Input A
Input B
Operating mode
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Indoor unit operating in power save mode, locked
Indoor unit operating in power save mode, unlocked
Indoor unit stopped, locked
Indoor unit operating not in power save mode, unlocked
Indoor unit operating in power save mode, locked
Indoor unit operating in power save mode, unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
CONTROL
MODE SWITCH
9
A