Setting and using method
12
Dry contact For Economizer
3. Setting the desired temperature
n
When setting the desired temperature of the Dry contact For
Economizer
: When operating the indoor unit, set the desired temperature according to the TEMP_SW setting.
When the indoor unit is unlocked, the desired temperature can be reset by other controller.
1) Turn on the TEMP_SETTING switch of SETTING_SW.
2) Use the TEMP_SW to set the temperature as shown below.
n
When not using the desired temperature setting of Dry
contact For Economizer
1) Turn off the TEMP_SETTING switch of SETTING_SW.
Ú
When operating the indoor unit initially with Dry contact For Economizer, set the desired temperature
to 18℃(64℉).
SETTING_SW
SETTING_SW
0
1
2
3
4
5
6
7
18(64) 19(66) 20(68) 21(70) 22(72) 23(74) 24(76) 25(77)
Desired temperature setting table
TEMP SW
setting
8
9
A
B
C
D
E
F
26(78) 27(80) 28(82) 29(84) 30(86) 30(86) 30(86) 30(86)
TEMP SW
setting
Temperature
setting °C(°F)
Temperature
setting °C(°F)