Airflow level
1/2 Balancing
0 CFM
340 CFM
Max. cool flow
340 CFM
Min. flow
340 CFM
Max. heat flow
340 CFM
Reheat flow
0 CFM
Airflow setpoint
Figure 12: Balancing PI 1 / 2 Display.
Pressure Independent, continued.
Configuration Parameter
BACnet
Function Description
Airflow Level
Read Only
AV110 (R)
Measured (calibrated) airflow.
Range: 0 to 20000 CFM (0 to 9440 l/s).
Airflow Setpoint
Read Only
AI350 (R)
Current active airflow setpoint.
Airflow Setpoint is not displayed when Damper Over-
ride is Open or Closed.
Range: 0 to 10000 CFM (0 to 4720 l/s).
Min. Flow (Minimum Airflow)
Default value: 340 CFM (160 l/s)
AV250 (R/W)
Minimum airflow supplied to the zone.
Range: 40 to 800 CFM (19 to 377 l/s).
Max. Cool Flow (Maximum Cooling
Airflow)
Default Value: 340 CFM (160 l/s)
AV252 (R/W)
Maximum airflow supplied to the zone when cooling.
Range: 40 to 800 CFM (19 to 377 l/s).
Max. Heat Flow (Maximum Heating
Airflow)
Default Value: 340 CFM (160 l/s)
AV251 (R/W)
Maximum airflow supplied to the zone when heating.
Range: 40 to 800 CFM (19 to 377 l/s).
Reheat Flow (Maximum Reheat
Airflow)
Default Value: 340 CFM (160 l/s)
AV253 (R/W)
Maximum airflow supplied to the zone with duct
reheat.
Range: 40 to 800 CFM (19 to 377 l/s).
Table 11: Pressure Independent Balancing Options Screen 1 of 2.