Outside Units
82
82
Heating Capacity
TC:Total Capacity(kW)
PI :Power Input(kW)
Combination
(%)
Inlet
Water
Temperature
(°C)
Water
Flow
Rate
(L/min)
Indoor Air Temperature(°CDB)
16
18
20
21
22
24
TC
(kW)
PI
(kW)
TC
(kW)
PI
(kW)
TC
(kW)
PI
(kW)
TC
(kW)
PI
(kW)
TC
(kW)
PI
(kW)
TC
(kW)
PI
(kW)
15
20
25
100
30
35
40
15
20
25
90
30
35
40
15
20
25
80
30
35
40
150
126.4 26.11 126.4 26.76 126.0 27.81 123.2 26.82 117.6 25.47 112.1 23.47
288
127.3 25.63 126.8 26.49 126.0 27.53 123.2 26.47 117.6 24.83 112.1 22.89
360
128.2 25.56 127.6 26.41 126.0 27.26 123.2 26.21 117.6 24.59 112.1 22.66
150
127.5 21.63 127.3 22.58 126.0 23.59 123.2 22.84 117.6 21.61 112.1 20.21
288
129.5 21.64 127.7 22.42 126.0 23.40 123.2 22.50 117.6 21.11 112.1 19.45
360
130.4 21.59 128.6 22.31 126.0 23.05 123.2 22.19 117.6 20.84 112.1 19.24
150
138.0 20.90 132.9 20.44 126.0 19.72 123.2 19.01 117.6 17.86 112.1 16.52
288
139.9 20.84 132.9 20.12 126.0 19.40 123.2 18.70 117.6 17.58 112.1 16.25
360
140.8 20.74 132.9 19.86 126.0 19.14 123.2 18.48 117.6 17.42 112.1 16.12
150
140.8 19.35 132.9 18.07 126.0 16.95 123.2 16.36 117.6 15.40 112.1 14.26
288
140.8 18.93 132.9 17.68 126.0 16.57 123.2 16.00 117.6 15.06 112.1 13.94
360
140.8 18.72 132.9 17.47 126.0 16.36 123.2 15.83 117.6 14.94 112.1 13.86
150
140.8 17.77 132.9 16.25 126.0 14.91 123.2 14.42 117.6 13.58 112.1 12.60
288
140.8 17.24 132.9 15.77 126.0 14.46 123.2 13.98 117.6 13.17 112.1 12.22
360
140.8 17.07 132.9 15.59 126.0 14.29 123.2 13.85 117.6 13.08 112.1 12.16
150
140.8 16.66 132.9 15.27 126.0 13.34 123.2 12.91 117.6 12.16 112.1 11.31
288
140.8 15.82 132.9 14.58 126.0 12.83 123.2 12.42 117.6 11.70 112.1 10.88
360
140.8 15.68 132.9 14.44 126.0 12.69 123.2 12.31 117.6 11.63 112.1 10.84
150
119.5 23.89 116.4 23.62 113.4 23.73 110.9 22.89 105.9 21.70 100.9 20.06
288
120.0 23.32 116.6 23.24 113.4 23.37 110.9 22.50 105.9 21.15 100.9 19.55
360
120.4 23.18 117.0 23.11 113.4 23.15 110.9 22.29 105.9 20.94 100.9 19.36
150
120.1 19.92 116.8 20.03 113.4 20.27 110.9 19.62 105.9 18.57 100.9 17.39
288
121.1 19.72 117.0 19.76 113.4 20.00 110.9 19.27 105.9 18.12 100.9 16.77
360
121.5 19.62 117.5 19.62 113.4 19.73 110.9 19.03 105.9 17.91 100.9 16.60
150
125.4 18.55 119.6 17.87 113.4 17.15 110.9 16.56 105.9 15.59 100.9 14.48
288
126.3 18.33 119.6 17.53 113.4 16.82 110.9 16.25 105.9 15.31 100.9 14.22
360
126.8 18.20 119.6 17.33 113.4 16.61 110.9 16.07 105.9 15.18 100.9 14.11
150
126.8 16.98 119.6 15.85 113.4 14.87 110.9 14.39 105.9 13.57 100.9 12.63
288
126.8 16.58 119.6 15.47 113.4 14.52 110.9 14.05 105.9 13.25 100.9 12.33
360
126.8 16.41 119.6 15.31 113.4 14.35 110.9 13.91 105.9 13.16 100.9 12.27
150
126.8 15.55 119.6 14.28 113.4 13.17 110.9 12.76 105.9 12.05 100.9 11.24
288
126.8 15.08 119.6 13.85 113.4 12.77 110.9 12.38 105.9 11.69 100.9 10.90
360
126.8 14.95 119.6 13.72 113.4 12.64 110.9 12.27 105.9 11.62 100.9 10.85
150
126.8 14.50 119.6 13.35 113.4 11.83 110.9 11.48 105.9 10.85 100.9 10.14
288
126.8 13.84 119.6 12.79 113.4 11.40 110.9 11.06 105.9 10.45 100.9 9.77
360
126.8 13.72 119.6 12.68 113.4 11.29 110.9 10.97 105.9 10.40 100.9 9.74
150
112.7 21.67 106.3 20.48 100.8 19.66 98.6 18.95 94.1 17.92 89.7 16.65
288
112.7 21.00 106.3 19.98 100.8 19.21 98.6 18.54 94.1 17.47 89.7 16.22
360
112.7 20.81 106.3 19.80 100.8 19.03 98.6 18.37 94.1 17.30 89.7 16.06
150
112.7 18.22 106.3 17.48 100.8 16.95 98.6 16.41 94.1 15.53 89.7 14.57
288
112.7 17.80 106.3 17.10 100.8 16.60 98.6 16.04 94.1 15.14 89.7 14.09
360
112.7 17.65 106.3 16.93 100.8 16.41 98.6 15.87 94.1 14.98 89.7 13.96
150
112.7 16.19 106.3 15.31 100.8 14.58 98.6 14.11 94.1 13.32 89.7 12.45
288
112.7 15.81 106.3 14.95 100.8 14.24 98.6 13.79 94.1 13.04 89.7 12.18
360
112.7 15.66 106.3 14.80 100.8 14.09 98.6 13.66 94.1 12.94 89.7 12.10
150
112.7 14.61 106.3 13.63 100.8 12.80 98.6 12.41 94.1 11.75 89.7 11.00
288
112.7 14.23 106.3 13.27 100.8 12.46 98.6 12.09 94.1 11.45 89.7 10.72
360
112.7 14.10 106.3 13.15 100.8 12.34 98.6 11.99 94.1 11.38 89.7 10.67
150
112.7 13.33 106.3 12.31 100.8 11.43 98.6 11.10 94.1 10.52 89.7 9.88
288
112.7 12.93 106.3 11.94 100.8 11.08 98.6 10.77 94.1 10.21 89.7 9.58
360
112.7 12.83 106.3 11.84 100.8 10.99 98.6 10.69 94.1 10.16 89.7 9.55
150
112.7 12.35 106.3 11.43 100.8 10.33 98.6 10.05 94.1 9.54 89.7 8.97
288
112.7 11.85 106.3 11.00 100.8 9.98 98.6 9.71 94.1 9.21 89.7 8.66
360
112.7 11.77 106.3 10.91 100.8 9.90 98.6 9.64 94.1 9.17 89.7 8.64