ELECTRICAL WIRING
71
ENGLISH
Target pressure adjusting
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn8” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“op1” ~ “op6” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn8” Push the ‘
●
’ button
Target pressure is set
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“HEAT” , “COOL” Push the ‘
●
’ button
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
Setting
Mode
low pressure
(kPa)
high pressure
(kPa)
off
778
2 990
op1
699
3 121
op2
739
2 827
op3
843
2 696
op4
908
2 565
op5
961
2 435
op6
1 026
2 304
Содержание MULTI V ARUN080LSH0
Страница 78: ...78 ENGLISH ...