4. Trouble Shooting
- 85 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
26
DC Compressor
Position
• Compressor
Starting fail error
• Check the connection of comp wire “U,V,W”
• Malfunction of compressor
• Check the component of “IPM”, detection parts.
Display
code
Title
Cause of error
Check point & Normal condition
■
Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
No
Yes
Yes
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
→
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
(0.188
±
7%)
2. Check insulation resistance between compressor
terminal and pipe (over 50M
Ω
)
→
Replace compressor if abnormality found
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
1. Check inverter PCB assembly U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
→
Reassemble if abnormality found
Is compressor
Wire connection
condition normal?
No
Yes
Check inverter PCB assembly IPM normality
→
Replace inverter PCB assembly
Is inverter PCB assembly normal?
No
Содержание Multi-Inverter Type
Страница 123: ...P NO MFL36552501 APRIL 2008 ...