- 47 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
4. Trouble Shooting
1.3 Error Indicator (Outdoor)
Outdoor Error
Ex) Error 21 (DC Peack)
1 Time
1 Time
1 Time
2 Times
2 Times
2 Times
1 Sec.
2 Sec.
2 Sec.
1 Sec.
1 Sec.
LED01G
(RED)
LED02G
(GREEN)
Error
Contents
LED01G/M
LED02G/M
Case of Error
Outdoor
Code
(Red)
(Green)
Status
21
DC Peak (IPM Fault)
2times
◑
1time
◑
Over Rated Current
Off
22
CT 2(Max CT)
2times
◑
2times
◑
Input Over Current
Off
23
DC Link Low Volt.
2times
◑
3times
◑
DC Link Volt is below 140Vdc
Off
24
L_P/H_P Switch
2times
◑
4times
◑
Low/High Press Switch Open
Off
25
Low Voltage/Over Voltage
2times
◑
5times
◑
Abnormal AC Volt Input
Off
26
DC Compressor Position Error
2times
◑
6times
◑
Compressor Starting Fall Error
Off
27
PSC/PFC Fault Error
2times
◑
7times
◑
Inverter PCB input current is over100A(peak) for 2us
Off
28
DC Link High Volt
2times
◑
8times
◑
Off
Off
29
COMP Over Current
2times
◑
9times
◑
Over Inverter Compressor Current
Off
31
CT Error
3times
◑
1time
◑
Low Current
Off
32
D-Pipe High (INV)
3times
◑
2times
◑
Off
Off
33
D-Pipe High (Normal)
3times
◑
3times
◑
Off
Off
40
CT Sensor (Open / Short)
4times
◑
O
CT Circuit Malfunction
Off
41
INV. D-Pipe Th Error
4times
◑
1time
◑
Open/Short
Off
44
Outdoor Air Th Error
4times
◑
4times
◑
Open/Short
Off
45
Cond. Pipe Th Error
4times
◑
5times
◑
Open/Short
Off
46
Suction Pipe Error
4times
◑
6times
◑
Open/Short
Off
47
Const D-Pipe Th Error
4times
◑
7times
◑
Open/Short
Off
51
Capacity Over
5times
◑
1time
◑
Over combination
Off
52
Signal Error(DSP Board <-> Main Board)
5times
◑
2times
◑
Communication Poorly
Off
53
Signal Error (Indoor <-> Outdoor)
5times
◑
3times
◑
Communication Poorly
Off
60
EEPROM Check Sum Error
6times
◑
O
Check Sum Mismatching
Off
61
Cond. Pipe Th High
6times
◑
1time
◑
Cond. Temp. High
Off
62
Heatsink Th High
6times
◑
2times
◑
Heatsink Temp. High
Off
63
Cond. Pipe Th Low
6times
◑
3times
◑
Cond. Temp. Low
Off
65
Heatsink Th Error
6times
◑
5times
◑
Open/Short
Off
67
Outdoor BLDC Fan Lock
6times
◑
7times
◑
Outdoor Fan is not operating
Off
73
PFC Fault Error(S/W)
7times
◑
3times
◑
Over Current of Outdoor Unit PFC
Off
Содержание Multi-Inverter Type
Страница 123: ...P NO MFL36552501 APRIL 2008 ...