4. Trouble Shooting
- 105 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
05
/
53
Title
Communication
(Indoor
→
Outdoor)
• Communication poorly
• Power input AC 220V. (Outdoor, Indoor)
• The connector for transmission is disconnected.
• The connecting wires are misconnected.
• The communication line is shorted at GND.
• Transmission circuit of outdoor PCB is abnormal.
• Transmission circuit of indoor PCB is abnormal.
Display
code
Title
Cause of error
Check point & Normal condition
Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
Adjust the connection of wire Confirm the wire of "Live",
"Neutral"
3. Check the resistance between communication line and
GND. (Normal : Over 2M
Ω
)
4. Check the connector for communication is correctly con-
nected.
5. If one indoor unit is operated normally, outdoor PCB is no
problem.
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at
outdoor unit.
6. If all indoor unit is displayed CH05 but outdoor PCB not
display
1) In Case of CH05, Check the Connection
→
CN-POWER, CN-COMM at the Main PCB
→
CN-MAIN at the Noise Filter
2) In Case of CH53, Check the Connection
→
CN-COMM at the Main PCB
→
CN-MAIN-COMM, CN-AC-220V at the Inverter PCB
→
CN- INVERTER at the Noise Filter
▶
▶
A7UW428FA3/A8UW488FA3/A9UW548FA3
CN-Power
CN-Power
CN-COMM
CN-COMM
CN-MAIN
CN-MAIN
CN-INVERTER
CN-INVERTER
CN-
CN-
AC-220V
AC-220V
CN-
CN-
MAIN-COMM
MAIN-COMM
< MAIN PCB >
< Noise Filter >
< INVERTER PCB >
CN-Power
CN-COMM
CN-MAIN
CN-INVERTER
CN-
AC-220V
CN-
MAIN-COMM