DUCT (LOW STATIC) INDOOR UNITS
External Static Pressure
Table 45:
Multi F Ceiling-Concealed Duct (Low Static) External Static Pressure Setting Values Table.
Static Pressure (in. wg)
0.0
0.04
0.08
0.12
0.16
0.20
Model No. / Nominal Capacity
of Indoor Unit (Btu/h)
Airflow Rate / CFM
Setting Value
LMDN096HV
9,000
High
318
98
103
108
116
123
130
Mid
247
82
88
94
102
110
118
Low
194
69
76
83
91
99
109
LMDN126HV
12,000
High
353
95
99
104
109
116
124
Mid
300
86
91
96
101
108
116
Low
247
78
82
87
93
100
108
LMDN186HV
18,000
High
530
123
125
129
134
141
145
Mid
441
109
112
117
123
129
136
Low
353
95
99
104
109
116
124
• To get the desired air flow and external static pressure combination, use the setting value from the table. Using a setting value other
than that listed in the table will not provide the desired combination.
• Table data is based at 230V. Air flow rate varies according to voltage fluctuation.
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.