Table 94:
DIP Switch Settings.
Dip Switch Settings
OFF
ON
Description
SW3
GROUP
Master
Slave
Group control setting using wired remote controller.
SW4
DRY
CONTACT
Variable
Auto
Dry contact mode setting.
1.
Variable: Auto/manual mode can be chosen using the wide wired
remote controller or wireless remote controller (factory setting is
the manual mode).
2.
Auto: For dry contact, it is always auto mode.
SW5
EXTRA1
Off
On
•
ON: Fan operates continuously.
•
OFF: Default (Fan does not operate continuously).
SW6
HEATER
Off
On
•
ON: Automatic heater operation.
•
OFF: Default (manual heater operation).
1. Indoor unit without electric heater.
• DIP switch 1, 2, 6, 8 must be set to OFF.
2. Indoor unit with electric heater, DIP switches 5 and 6 must be set to ON.
•
SW 5 ON: Fan operates continuously. (Can have uninterrupted heating during defrost or oil return modes using continuous heater and
fan operation.)
•
SW5 OFF: Fan discontinuous operation. (There would be reduction in heating capacity while defrosting or oil return operation.)
•
SW6 ON: Automatic heater operation. (Heater operates automatically using the heater algorithm.)
•
SW6 OFF: Manual heater operation. (On / off operation is set manually. Heater operation follows the heater algorithm.)