General Data / Specifications
Model Name
LMCN077HV
LMCN097HV
LMCN125HV
LMCN185HV
Nominal Cooling Capacity (Btu/h)
1
7,000
9,000
12,000
18,000
Nominal Heating Capacity (Btu/h)
1
8,100
10,400
13,800
20,800
Operating Range
Cooling (°F WB)
57-77
Heating (°F DB)
59-81
Fan
Type
Turbo
Motor Output (W) x Qty.
43 x 1
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate CFM (H/M/L)
265 / 212 / 177
300 / 265 / 230
335 / 283 / 247
459 / 424 / 388
Unit Data
Refrigerant Type
2
R410A
Refrigerant Control
EEV
Power Supply V, Ø, Hz
3
208-230, 1, 60
Rated Amps (A)
0.25
Sound Pressure Level ±3 dB(A) (H/M/L)
4
31 / 27 / 24
36 / 33 / 30
38 / 35 / 32
38 / 37 / 34
Body Dimensions (W x H x D, in.)
22-7/16 x 8-7/16 x 22-7/16
22-7/16 x 10-3/32 x 22-7/16
Grille (PT-UQC, sold separately) Dimensions (WxHxD, in.)
27-9/16 x 7/8 x 27-9/16
Body Net Weight (lbs.)
31
34
Grille (PT-UQC, sold separately) Net Weight (lbs.)
7
Body Shipping Weight (lbs.)
34
36
40
42
Grille (PT-UQC, sold separately) Shipping Weight (lbs.)
11
11
Power Wiring / Communications Cable (No. x AWG)
5
4 x 18
Heat Exchanger (Row x Column x Fin / inch) x Number
(2 x 8 x 18) x 1
(2 x 10 x 18) x 1
Piping
Liquid (in.)
1/4
1/4
Vapor (in.)
3/8
1/2
Drain O.D. / I.D. (in.)
1-1/4, 1
1
Nominal capacity is rated 0 ft. above sea level with a 0 ft. level difference between outdoor and indoor
units. All capacities are net with a combination ratio between 95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
This unit comes with a dry helium charge.
3
Acceptable operating voltage: 187V-253V.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
same in both cooling and heating mode. These values can increase due to ambient conditions during
operation.
5
All power wiring / communications cables to be minimum 18 AWG, 4-conductor, stranded, shielded,
and must comply with applicable local and national codes.
Table 71:Multi F Four-Way Ceiling-Cassette Indoor Unit General Data.
FOUR-WAY CEILING-CASSETTE INDOOR UNITS
CEILING-CASSETTE | 131
Four-W
ay Ceiling-Cassette
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F