31
MAX COMBINATION CAPACITY
ENGLISH
Multi Piping Type
The combination of indoor unit is to be decided that the sum of indoor unit capacity index must
be smaller than the maximum combination capacity of outdoor unit. We recommend to calculate
indoor unit capacity like below.
If you do not follow our recommendation, it will have some problems in low ambient condition
i.e. some indoor unit will not be able to heat very well in heating mode.
CALCULATION METHOD FOR THE CONNECTABLE TOTAL CAPACITY OF INDOOR UNIT
Sum up the capacity of all indoor unit, but high static duct type indoor unit capacity weights 1.3
times
Ex)
1
Outdoor unit : A9UW566FA3(FM56AH)(connectable maximum capacity is 73kBtu)
Indoor unit:
AMNH186BHA0[MB18AH],AMNH246BHA0[MB24AH],AMNH246BHA0[MB24AH]
(18 + 24 + 24) x 1.3 = 66 x 1.3 = 85.8kBtu: this combination has a some problem
2
Out door unit: FM56AH
Indoor unit:
AMNH186BHA0[MB18AH],AMNH246BHA0[MB24AH],AMNH18GD5L0[MS18AH]
(18 + 24) x 1.3 + 18 + 72.6: this combination can be ok
Capacity
(kBtu/h)
Max Room No. Combination Indoor Capacity
(kBtu/h)
Max Combination Capacity
(kBtu/h)
14
2
5, 7, 9, 12
21
16
2
5, 7, 9, 12, 15
24
18
3
5, 7, 9, 12, 15
30
21
3
5, 7, 9, 12, 15, 18
33
24
4
5, 7, 9, 12, 15, 18
39
27
4
5, 7, 9, 12, 15, 18, 24
41
30
5
5, 7, 9, 12, 15, 18, 24
48
MAX COMBINATION CAPACITY
ENGLISH
Содержание MU2R15
Страница 26: ...FUNCTION 26 14 16 1Ø kBtu h 1Ø kBtu h 27 30 18 21 24 1Ø kBtu h DIPSW1 5 DIPSW1 5 DIPSW1 5 ENGLISH ...
Страница 122: ...FONCTION 25 FRANÇAIS 14 16 1Ø kBtu h 40 1Ø kBtu h 27 30 1Ø kBtu h DIP SW 18 21 24 1Ø kBtu h SW01N DIP_SW01D 5 DIP_SW1 5 ...
Страница 154: ...FUNKTION 25 DEUTSCH 14 16 1Ø kBtu h 40 1Ø kBtu h 27 30 1Ø kBtu h DIP SW 18 21 24 1Ø kBtu h SW01N DIP_SW01D 5 DIP_SW1 5 ...
Страница 218: ...FUNKCE 25 ČEŠTINA 14 16 1Ø kBtu h 40 1Ø kBtu h 27 30 1Ø kBtu h DIP SW 18 21 24 1Ø kBtu h SW01N DIP_SW01D 5 DIP_SW1 5 ...
Страница 282: ...FUNKCJA 25 POLSKI 14 16 1Ø kBtu h 40 1Ø kBtu h 27 30 1Ø kBtu h DIP SW 18 21 24 1Ø kBtu h SW01N DIP_SW01D 5 DIP_SW1 5 ...
Страница 482: ......