Heat insulation

- Use the heat insulation material for the

refrigerant piping which has an excellent
heat-resistance (over 120°C).

- Precautions in high humidity circumstance:

This air conditioner has been tested accord-
ing to the "KS Standard Conditions with Mist"
and confirmed that there is not any default.
However, if it is operated for a long time in
high humid atmosphere (dew point tempera-
ture: more than 23°C), water drops are liable
to fall. In this case, add heat insulation mate-
rial according to the following procedure:

• Heat insulation material to be prepared...

Adiabatic EPDM or NBR with thickness 10
to 20mm.

• Stick EPDM or NBR on all air conditioners

that are located in ceiling atmosphere.

• In addition to the normal heat insulation

(thickness: more than 8mm) for refrigerant
piping (gas piping: thick piping) and drain
piping, add further 10mm to 30mm thick-
ness material.

Wiring Connection

- Open the control box cover and connect the

Remote controller cord and Indoor power
wires.

- Remove the control box cover for electrical

connection between the indoor and outdoor
unit.

- Use the cord clamper to fix the cord.

THE INDOOR UNIT INSTALLATION

10

ENGLISH

Indoor
unit

Thermal insulator 
(accessory)

Fastening band 
(accessory)

Refrigerant 
piping

Wired Remote
Controller Cord
(there is no need in case of
Wireless Remote Controller)

Control box cover
(On which the Electric
Connection cord Wiring
Connection is put)

Connection cord
between the indoor unit
and the outdoor unit

20mm

GN/YL

NORMAL
CROSS-SECTIONAL
AREA 0.75mm

CAUTION

• The connecting cable connected to the

indoor and outdoor unit should be com-
plied with the following specifications
(Rubber insulation, type H05RN-F
approved by HAR or SAA).

• If the supply cord is damaged, it must be

replaced by a special cord or assembly
available from the manufacturer of its
service agent.

!

Содержание MFL67500701

Страница 1: ... completely before installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly TYPE 4 WAY CEILING CASSETTE Cooling only Inverter ENGLISH ...

Страница 2: ...condition er is used for many hours Clean the air filter once every 2 weeks Dust and impurities collected in the air filter may block the air flow or weaken the cooling dehumidifying functions For your records Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes Write the model number and the serial number here Model number Serial number You c...

Страница 3: ... a dedicated circuit There is risk of fire or electric shock For electrical work contact the dealer seller a qualified electrician or an Authorized Service Center Do not disassemble or repair the product There is risk of fire or electric shock Always ground the product There is risk of fire or electric shock Install the panel and the cover of control box securely There is risk of fire or electric ...

Страница 4: ...CAUTION Installation Always check for gas refrigerant leakage after installation or repair of product Low refrigerant levels may cause failure of product Install the drain hose to ensure that water is drained away properly A bad connection may cause water leakage Keep level even when installing the product To avoid vibration or water leakage Do not install the product where the noise or hot air fr...

Страница 5: ...RY 14 TEST RUNNING 14 Precautions in test running 14 Check the following items when installa tion is complete 14 Connection of power supply 14 Evaluation of the performance 15 Hand over 16 INSTALLATION INSTRUCTIONS 16 Installer Setting How to enter installer setting mode 17 Installer Setting Installer Setting Code Table 18 Installer Setting Setting Address of Central Control 18 Installer Setting C...

Страница 6: ...way Ensure the spaces indicated by arrows from the wall ceiling or other obstacles The indoor unit must keep the maintenance space Unit mm Ceiling Ceiling Board Ceiling Board Above 2500 3600 or less 1000 or more 1500 or more 1500 or more 300 or less Floor 200 or more Please use an annexed sheet or the corru gated cardboard on the bottom of packing as installation sheet When using the bottom sheet ...

Страница 7: ...e 840 Unit size CAUTION This air conditioner uses a drain pump Install the unit horizontally using a level gauge During the installation care should be taken not to damage electric wires Select and mark the position for fixing bolts and piping hole Decide the position for fixing bolts slight ly tilted to the drain direction after con sidering the direction of drain hose Drill the hole for anchor b...

Страница 8: ...ient for drain Should be 1 50 1 100 THE INDOOR UNIT INSTALLATION 8 ENGLISH NOTE Avoid the following installation location 1 Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated These may cause heat exchange efficiency reduction or water drops drain pump mal function In these cases take the following actions Make sure that ventilation fan is enough to...

Страница 9: ...the following procedure to test the drain pump operation Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end Feed water to the flexible drain hose and check the piping for leakage Be sure to check the drain pump for normal operating and noise when electrical wiring is complete When the test is complete connect the flexi ble drain hose to the drain ...

Страница 10: ...d drain piping add further 10mm to 30mm thick ness material Wiring Connection Open the control box cover and connect the Remote controller cord and Indoor power wires Remove the control box cover for electrical connection between the indoor and outdoor unit Use the cord clamper to fix the cord THE INDOOR UNIT INSTALLATION 10 ENGLISH Indoor unit Thermal insulator accessory Fastening band accessory ...

Страница 11: ...not connect wiring of different thickness es to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is the same thickness do as shown in the figure below 11 INSTALLATION ENGLISH Electricwire Round crimp style terminal Attach insulation sleeve WARNING Make sure that the screws of the termi nal are free from looseness ...

Страница 12: ... Do not tighten the bolts completely The fixing screws are included in the indoor unit box Check the alignment of panel with the ceil ing Height can be adjusted using hanging bolts as shown in picture Insert the other two screws and tighten all screws com pletely 5 Fit the corner covers Front grille Coner cover Hook clip Hook INSTALLATION TO DECORATIVE PANEL ACCESSORY INSTALLATION TO DECORATIVE PA...

Страница 13: ...rol box 9 Install the air inlet grille and filter on the panel Screw Air conditioner unit Decorative panel Fit the insulator this part and be careful for cool air leakage Good example Ceiling board Ceiling board Decorative panel Air Cool air leakage no good Bad example Air conditioner unit CN VANE 1 2 CN DISPLAY 13 INSTALLATION TO DECORATIVE PANEL ACCESSORY ENGLISH CAUTION Install certainly the de...

Страница 14: ...h Is the heat insulation complete refrigerant and drain piping Is there any leakage of refrigerant Is the remote controller switch operated Is there any faulty wiring Are not terminal screws loosened M4 118N cm 12kgf cm M5 196N cm 20kgf cm M6 245N cm 25kgf cm M8 588N cm 60kgf cm Connection of power supply Connect the power supply cord to the inde pendent power supply Circuit breaker is required Op...

Страница 15: ...urn out of the wires Specification of power source Confirm that electrical capacity is suffi cient Be sure that the starting voltage is main tained at more than 90 percent of the rated voltage marked on the name plate Confirm that the cable thickness is as specified in the power sources specifica tion Particularly note the relation between cable length and thickness Never fail to equip a leakage b...

Страница 16: ...ON Installer setting mode is to set the detail function of the remote controller If the installer setting mode is not set correctly it can cause problems to the product user injury or property damage This must be set by an certificated installer and any installation or change that is carried out by a non certificated person should be responsible for the results In this case free service cannot be ...

Страница 17: ...he product turn off the power then turn it back on after 1 minute Auxiliary heater This function is only applied to models with Auxiliary Heater function being activated Installer Setting Installer Setting Code Table No Function Function Code Setting Value Remote Controller LCD 0 Mode Override 0 0 Set to Master 1 Set to Slave 1 Ceiling Height Selection 1 1 Standard 2 Low 3 High 4 Super High 2 Grou...

Страница 18: ...e and method can differ by the indoor unit type 3 Reset the remote controller to use the general operation mode 1 With the MODE button pressed press the RESET button 2 By using the temperature setting button set the indoor unit address Setting range 00 FF 3 After setting the address press the ON OFF button toward the indoor unit 1 time 4 The indoor unit will display the set address to complete the...

Страница 19: ......

Отзывы: