- The following parts is option.
Hanging Bolt - W 3/8 or M10
Nut - W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
Air conditioner
Take enough
distance
Set screw of
paper model (4 pieces)
Paper model
for installation
Ceiling board
150mm
Ceiling board
Ceiling
Keep the length of the bolt
from the bracket to 40mm
Open the ceiling board
along the outer edge of the
paper model
Flat washer for M10
(accessory)
Hanging bolt
(W
3
/8 or M10)
Nut
(W
3
/8 or M10)
Nut
(W
3
/8 or M10)
Spring washer
(M10)
Air Conditioner body
Keep the length of 15~18mm
between the air conditioner
bottom surface and the ceiling
surface
Flat washer for M10
(Attached Insulator,
accessory)
Wall
Indoor
Outdoor
Slope gradient for
drain Should be
1/50 ~ 1/100
THE INDOOR UNIT INSTALLATION
8
ENGLISH
NOTE
!
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it
may not suck oily steam.
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
CAUTION
Tighten the nut and bolt to prevent unit
falling.
• Drill the piping hole on the wall slightly
tilted to the outdoor side using a Ø 70
hole-core drill.
!