18
WIRING CONNECTION
ENGLISH
WIRING CONNECTION
Electrical Wiring
- All wiring must comply with local require-
ments.
- Select a power source that is capable of sup-
plying the current required by the air condi-
tioner.
- Use a recognized circuit breaker between
the power source and the unit. A disconnec-
tion device to adequately disconnect all sup-
ply lines must be fitted.
- Capacity of circuit breaker recommended by
authorized personnel only.
Indoor unit
- Remove the control box cover for electrical
connection between the indoor and outdoor
unit.
- Use the cord clamper to fix the cord.
Outdoor unit
- Remove the control cover for wiring connec-
tion.
- Use the cord clamper to fix the cord.
- Earthing work
Case 1 :Terminal block of Outdoor Unit have
mark.
Connect the cable of diameter 1.6mm
2
or
more to the earthing terminal provided in the
control box and do earthing.
Case 2 :Terminal block of Outdoor Unit don't
have mark.
- Connect the cable of diameter 1.6mm
2
or
more, to the panel of control box, marked as
and fasten with earth screw.
Outdoor
Indoor
Main
power source
Switch box
Circuit Breaker
Main terminal
board
Control terminal
board
Cord
clamper
Side panel
A view
Remote
control cord
Connection
cord between
the indoor unit
and the
outdoor unit
Motor PCB
Main PCB
Control box cover
(On which the Electric
Wiring Connection is put)
A
Capacity(Btu/h)
Phase(Ø)
Circuit Breaker
42 k
1
35A
48 k
1
35A
55 k
1
35A
• The circuit diagram is not subject to
change without notice.
• Be sure to connect wires according to
the wiring diagram.
• Connect the wires firmly, so that not to
be pulled out easily.
• Connect the wires according to color
codes by referring the wiring diagram.
CAUTION
!
Содержание MFL62541004