External Static Pressure(Pa)
60
(Low
EPS)
80
100
120
130
(High
EPS)
140
160
180
200
Model
(Capacity)
Step
42 kBtu/h
Hi (48 CMM)
92
96
101
106
113
116
120
124
126
Med(42 CMM)
86
90
96
101
106
110
114
119
121
Low(36 CMM)
80
86
92
96
101
105
109
113
115
48 kBtu/h
55 kBtu/h
Hi (60 CMM)
101
105
108
112
117
120
124
127
129
Med(50 CMM)
90
97
101
107
113
114
117
120
122
Low(40 CMM)
86
90
93
96
103
107
110
113
115
24
EXTERNAL STATIC PRESSURE & FLOW
ENGLISH
EXTERNAL STATIC PRESSURE & FLOW
How to set Remote Controller's Switch 2
NOTE
!
Capacities are tested in the following conditions.
Static
Pressure
(Pa)
Voltage
(Phase/Volt)
Air Flow
Step
Piping
Length
Temperaure(°C DB/°C WB)
Cooling
Heating
Indoor
Outdoor
Indoor
Outdoor
60
Ø1/230 V
High
7.5 m
27/19
35/24
20/15
7/6
Remote Controller
For Low E.S.P Mode
For High E.S.P Mode
S/W 2
1
1. Low/Low E.S.P
2. Standard/high E.S.P
3. High/high E.S.P
3
2
How to set RPM
ZONE 1
ZONE 2
ZONE 3
ZONE 4
AUTO INDOOR
REMO
ZONE 1
ZONE 2
ZONE 3
ZONE 4
2TH
REMO
AUTO INDOOR
100 unit
10 unit
1
Press the
button.
2
Press the
button.
4
If you press the
button one more time, the E.S.P
value will be set and the setting mode will be unset.
3
Set the volume of each air flow (Lo
’
Med
’
Hi) by using the
button. Press the
button to select the air flow.
(The value of E.S.P could be adjusted from 1 to 255.)
(Ex. The figure on the left shows when the strong
wind’s ESP value has been set to
127. 127 means 1270 RPM).