2. Indoor unit installation
■
Installation of Unit
Unit should be installed for horizontal and verti-
cal discharge application only.
• Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
• Install the unit leaning to a drainage hole side as
a figure for easy water drainage.
• A place where the unit will be leveled and that
can support the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
90
400
94
2
3
94
A
650
400
90
B
C
1
1
Suspension
bolts
Spring
washer
Max.
12mm
Washer
Nut
A
B
C
Dimension
Capacity
36K BTU/h
1550
1362
236
42K BTU/h
1550
1362
236
48K BTU/h
1550
1362
272
60K BTU/h
1550
1362
292