CHECKING FLOW CHART BY FAILURE
Yes
Is the DLB relay normal?
Measure the resistance
Normal : infinite
Abnormal : shorted
No
Replace the
relay PCB
3
Tap 01 and Tap02 : Ry 1
DLB
Relay
Is the value of thermistor
normal? (Refer below)
Check with the test mode
Yes
Replace the
Main PCB
4
Plug in the unit
To enter the test mode, follow these steps:
1. Press the any button, and Mode knob is
placed in the Off
2. Press the "4" and "6" key at the same time for
1 second.
3. Press the "4" and "6" key at the same time for
1 second again.
4. Press the “3” key.
Current temp
Normal : Thermistor value at room temp is from
70˚F to 90
˚
F