- 21 -
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidifica-
tion operation and 4-min compressor off repeat.
Compressor ON Temp.
➲
Setting Temp+0.5°C
Compressor OFF Temp.
➲
Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
■
Heating Mode Operation(H/P model)
• When the intake air temp r3°…above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on.
Compressor ON Temp.
➲
Setting Temp.
Compressor OFF Temp.
➲
Setting Temp.+3°C
• While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C ,
it operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it
operates with Super-Low(while in sleep mode, with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C ,
it operates with the low airflow speed.
• If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
• While in defrost control, both of the indoor and outdoor fans are turned off.
■
Defrost Control(H/P model)
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 60 minutes passed
from starting of heating operation and more than 10 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation or after the outdoor fan operates
within max. 2 minutes 30 seconds when the outdoor pipe temperature rises over 12°C even it before 12
minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 60 minutes passed
from ending of the first defrost and more than 10 minutes operation of compressor.
■
Cooling overload
• Control indoor fan by sensing outdoor pipe temperature.
• One step down from setting fan speed if pipe temperature is oven 50°C and if below 45°C, operate on set-
ting temperature.
• One of the outdoor fan is OFF if pipe temperature is below 0°C and outdoor fan is ON if pipe temperature is
over 0°C.
■
Heating overload(H/P models)
• Outdoor fan ON/OFF by sensing outdoor pipe temperature.
• Outdoor fan is OFF if pipe temperature is over 6.5°C and outdoor fan is ON if pipe temperature is below
0°C.
• Outdoor fan is off if any one part is heating overload condition.
Содержание LM-2422A2L/A3L
Страница 12: ... 12 900 1 225 370 2 3 LM 4822C3L LM 4822A3L ...
Страница 59: ... 59 2 Outdoor 2 1 MAIN P C B ASM LM 2422C2L LM 2422A2L LM 3625C3L A3L LM 3626A3L LM 4822C3L LM 4822A3L ...
Страница 60: ... 60 3 Display Assembly ...
Страница 61: ... 61 Schematic Diagram 1 Indoor 1 1 LM 2422C2L LM 2422A2L LM 3625C3L A3L LM 3626A3L LM 4822C3L LM 4822A3L ...
Страница 62: ... 62 1 2 LM 3620C2L LM 3622A2L LM 3620A2L ...
Страница 63: ... 63 2 Outdoor 2 1 LM 2422C2L LM 2422A2L ...
Страница 64: ... 64 2 2 LM 3625C3L A3L LM 3626A3L ...
Страница 65: ... 65 2 3 LM 4822C3L LM 4822A3L ...
Страница 81: ...P No 3828A20095K January 2005 Printed in Korea ...