When product is operating normally, but there is no cool air from all three indoor unit.
Check as follows.(LM-3022C3L)
- 39 -
No cool air from all three indoor unit
Compressor is operating normally.
Outdoor unit is clogged by extraneous substances.
Cool air from indoor unit
Remove it and turn off Main Power Source.
Turn on Main Power.
Operating after 3 minutes
Check refrigerant pressure
(Suction pressure is usually 4.5~6.0kg/cm
2
)
at normal condition.
Recharge refrigerant