* The branch-circuit conductors are sized at 125 percent of the larger motor-compressor current,
plus the sum of the rated-load currents of the other loads [440.32].
* The disconnecting means for air-conditioning or refrigeration equipment must be located within
sight from and readily accessible from the equipment. “Within Sight” is visible and not more
than 50 ft(15.24 m) from each other [Article 100].
* Circuit Breaker as per NEC 440.22 (B) (1)
MODEL
CONDENSER EVAPORATOR
MFCB BCCS MOC
Compressor
Condenser
Fan
SUPPLY
BLOWER
MOTOR
(kW)
FLA
RLA LRA FLA
LK-C0608A 11.0
65.5
1.4
0.75
2.0
26
20
16
LK-C0728A 13.0
75
1.4
0.75
2.0
26
20
16
LK-C0908A 15.0
100
2.0
1.1
2.7
31
23
20
LK-C1058A 16.8
114
2.0
1.5
3.5
35
26
24
RLA - Rated Load Current
LRA- Locked Rotor Current
FLA- Full Load Amps
MFCB- Maximum Fuse Circuit Breaker
BCCS- Branch Circuit Conductor Size Amps
Electric Characteristics