Type
Single Zone Ceiling-Concealed Duct (High Static)
System (Model) (Indoor Unit / Outdoor Unit)
LH247HV (LHN247HV / LUU247HV)
LH367HV (LHN367HV / LUU367HV)
Nominal Cooling Capacity (Btu/h)
24,000
36,000
Cooling Power Input
1
(kW)
2.0
2.91
Nominal Heating Capacity (Btu/h)
27,000
40,000
Heating Power Input
1
(kW)
2.28
3.36
Power Supply V, Ø, Hz
2
208-230 / 1 / 60
Outdoor Unit Operating Range
Cooling (°F DB)
5-118
Heating (°F WB)
0-64
Indoor Unit Operating Range
Cooling (°F WB)
57-77
Heating (°F DB)
59-81
Indoor Temperature Setting Range
Cooling (°F)
65-86
Heating (°F)
61-86
Unit Data
Refrigerant Type
3
R410A
Refrigerant Control
EEV
Indoor Unit Sound Pressure Level ±3 dB(A) (H/M/L)
4
38 / 36 / 35
39 / 38 / 37
Outdoor Unit Sound Pressure Level ±3 dB(A) (Cool/Heat)
4
48 / 52
52 / 54
Indoor Unit Net / Shipping Weight (lbs.)
73 / 95
125 / 139
Outdoor Unit Net / Shipping Weight (lbs.)
133 / 146
203 / 227
Power Wiring / Communications Cable (No. x AWG)
2
4 x 18
Power Supply (No. AWG)
3 x 12
Compressor (Type x Qty.)
Twin Rotary x 1
Fan
Indoor Unit Type x Qty.
Sirocco x 1
Outdoor Unit Type x Qty.
Propeller x 1
Propeller x 2
Motor / Drive
Brushless Digitally Controlled / Direct
Airflow Rate
Indoor Unit (Max. / H / M / L [CFM])
688 / 618 / 530
1,130 / 953 / 706
Outdoor Unit (CFM)
2,048
1,942 x 2
Factory Set (High) External Static Pressure (in. wg)
0.39
Piping
Liquid (in.)
3/8
Vapor (in.)
5/8
Indoor Unit Condensate Drain O.D. / I.D. (in.)
1-1/4 / 1
Additional Refrigerant Charge (oz./ft.)
0.43
Maximum Pipe Length (ft.)
164
246
Piping Length (no additional refrigerant, ft.)
25
Maximum Elevation Difference (ft.)
98
Table 2: Ceiling-Concealed Duct (High Static) System General Data.
general data / SPeCiFiCationS
EEV: Electronic Expansion Valve
IDU: Indoor Unit
ODU: outdoor Unit
Power wiring is field supplied and must comply with the applicable local and national codes.
This unit comes with a dry helium charge.
This data is rated 0 ft above sea level, with 24.6 ft of refrigerant line per indoor unit and a 0 ft level differ-
ence between outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb
(WB); and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet
bulb (WB); and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1
Power Input is rated at high speed.
2
All power/communication cables to be minimum 18 AWG, 4-conductor, stranded, shielded and must
comply with applicable and national code.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
same in both cooling and heating mode. These values can increase due to ambient conditions during
operation.
duct (HIgH StatIc) | 9
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Содержание LH247HV
Страница 29: ... Cooling Capacity Data on page 30 Heating Capacity Data on page 32 PERFORMANCE DATA ...
Страница 69: ......
Страница 70: ......
Страница 71: ......