Before specifying or placing an order, refer to the V-Net Network Solutions Engineering Product Data Book, and review the detailed technical data provided to fully understand the capabilities and limitations of
these devices.
For information on controller capabilities, refer to the Controls and Options Table on page 27.
Specialty Application
Device
Name
Model No.
Connects
to
Application
Binary Signals
Input / Output
Description
Dry Contact Unit
24 VAC
PQDSB1
Indoor
Unit
ON / OFF, Run Status,
Error Status
1 / 2
Enables the indoor unit to be
controlled and monitored by
third-party controls using
binary inputs and outputs.
Dry Contact Unit
for Setback
PQDSBC
ON / OFF, Mode, Controller
Lock, Power Save, Run
Status, Error Status
2 / 2
Dry Contact Unit
for Thermostat PQDSBNGCM1
ON / OFF, Thermo ON /
OFF, Mode, Fan Speed,
Run Status, Error Status
—
Enables the indoor unit to be
controlled and monitored by a
third-party thermostat or controller.
PI-485 V-net
Control
Integration
Board
PMNFP14A0/A1 Outdoor
Unit
—
—
Control integration to LG V-net
controls (AC Smart Premium, ACP,
BACnet, LonWorks, etc.)
Digital Output
(DO) Kit
PQNFP00T0
Comm.
BUS
ON / OFF
0 / 1
One 25A DPST normally open
relay. Used with central
controller to control third-party
device manually or by
schedule.
Table 12: Summary Data—Specialty Application Devices.
aCCeSSorieS
Speciality application devices
duct (HIgH StatIc) | 25
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Содержание LH247HV
Страница 29: ... Cooling Capacity Data on page 30 Heating Capacity Data on page 32 PERFORMANCE DATA ...
Страница 69: ......
Страница 70: ......
Страница 71: ......