eXternal StatiC PreSSure
Table 5: Ceiling-Concealed Duct (High Static) Indoor Unit External Static Pressure Setting Values Table.
•
To get the desired air flow and external static pressure combination, use the setting value from the table. Using a setting value other
than that listed in the table will not provide the desired combination.
•
Table data is based at 230V. Air flow rate varies according to voltage fluctuation.
Static Pressure (in. wg)
0.1
0.15
0.23
0.31
0.39
0.47
0.55
0.60
0.62
0.70
0.78
Model No. / Nominal Capacity
of System (Btu/h)
Airflow Rate / CFM
Setting Value (in. wg)
LHN247HV
24,000
High
688
90
97
108
119
126
134
143
146
149
157
159
Mid
618
86
93
105
115
123
131
140
143
146
153
156
Low
530
82
90
102
112
120
128
137
140
143
150
153
LHN367HV
36,000
High
1,130
-
96
103
109
115
120
126
129
-
-
-
Mid
953
-
85
96
102
109
115
121
124
-
-
-
Low
706
-
76
85
95
100
107
113
116
-
-
-
Indoor units
Setting the external Static Pressure on the remote Controller
Use this function to set the wind strength for each airflow level.
TEMP
FAN
SPEED
OPER
MODE
To access the controller set mode, press the
and buttons simultaneously for >three (3)
* External Static Pressure Code: 03
1
Select the desired air flow rate with the
button.
2
Select the desired air flow rate value with
the temperature up), down) button.
* External Static Pressure value range: 0~255
- External Static Pressure value will be displayed
at the upper right-hand section of the screen.
3
Press the button to save / set the chosen
External Static Pressure value.
4
To deactivate the controller set mode, press the
and buttons simultaneously for > three (3) seconds.
- If there is no input (no buttons pressed) for
more than 25 seconds, the controller set mode
will automatically deactivate.
5
OPER
MODE
FAN
SPEED
OPER
MODE
seconds.
(Choose from SLo→Lo→Med→Hi→Po.)
•
The external static pressure must be set by a trained service provider, and it must be set correctly. If the external static pressure is
set incorrectly, the product may malfunction.
•
Do not alter the external static pressure value that corresponds to each airflow level.
•
External static pressure values vary according to the model.
•
When the airflow rate is increased to a higher value, during the external static value setup, the previous airflow value will be stored in
the system memory. (External static pressure values are saved to system memory before the changes are implemented).
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
16 | duct (HIgH StatIc)
Ceiling-Concealed Duct (High Static) System Engineering Manual