- 27 -
0
Short
Open
Normal
Change the sensor
Replace the refrigerator
Check the Temp and
resistance (Table-3)
Result
SVC Action
8-4 Defrost Sensor Error (F dS)
No
1
2
Checking flow
Check for a loose connection.
Check the Orange to Orange.
Result & SVC Action
Check the Brown to Brown.
<Temperature table-3>
(1) To (2)
23°F
°C
32°F
°C
41°F
°C
50°F
°C
59°F
°C
Result
38
30
24
19.5
16
The sensor is determined by
the temperature.
For example, 24
indicates 41°F.
<CON7>
(1)
(2)
(1)
(2)