1.Selection
ofthe
bestlocation
1)Indoor
unit
Selectlocation
Installthe
airconditioner
inthe
locationthat
satisfiesthe
followingconditions.
•The
placeshall
easilybear
aload
exceeding
fourtimes
theindoor
unit’s
weight.
•The
placeshall
beable
toinspect
theunit
as
thefigure.
•T
heplace
wherethe
unitshall
beleveled.
•The
placeshall
alloweasy
water
drainage.(Suitabledimension
“H”is
necessary
toget
aslope
todrain
asfigure.)
•Theplace
shalleasily
connectwith
the
outdoorunit.
•The
placewhere
theunit
isnot
affected
byan
electricalnoise.
•The
placewhere
aircirculation
inthe
roomwill
begood
.
•There
shouldnot
beany
heatsource
orsteam
nearthe
unit
2)Outdoor
unit
•I f
anawning
isbuilt
overthe
unitto
prevent
directsunlight
orrain
exposure,be
careful
thatheat
radiationfrom
thecondenser
isnot
restricted.
•There
shouldnot
beany
animalsor
plants
whichcould
beaf
fectedb
yhot
air
discharged.
•Ensure
thespaces
indicatedby
arrowsfrom
thewall,
ceiling,fence
orother
obstacles.
3)Piping
lengthand
theelevation
5
Indoor unit
Outdoor unit
B
A
H
1000
600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
2.Installation
ofIndoor
,Outdoor
Unit
Capacity
Gas
Liquid
Elevation B(m)
Length A(m)
*Additional
refrigerant
(g/m)
Pipe Size
(Diameter : Ø)
Standard
Standard
Max.
Max.
66K BTU/h
70
7/8"
1/2"
7.5
5
30
10
Indoor
Unit
(nos)
Outdoor
Unit
(nos)
1
1
• Capacity
is
based
on
standard
length
and
maximum
allowance
lengthis
onthe
basisof
reliability.