52 Multi Air Conditioner
Installation
(3) Connecting Pipings and the cable to Outdoor unit
Outdoor unit
A-UNIT
Gas side piping
Liquid side piping
B-UNIT
Torque wrench
1) Connecting the pipings to the Outdoor
unit
1. Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
2. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the
arrow on the wrench.
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of
wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductors.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and
make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the
wires.)
4) Specification of power source.
5) Confirm that electrical capacity is sufficient.
6) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
• Proper starting power is not given to the compressor.
Pipe Size
Torque
Liquid Side (1/4")
1.8kg m
Liquid Side (3/8")
4.2kg m
Gas Side (1/2")
5.5kg m
Gas Side (5/8")
6.6kg m
Содержание L2-C242GL0
Страница 13: ...Service Manual 13 Dimensions 900 1 225 370 L3 C482LL0 ...
Страница 18: ...18 Multi Air Conditioner Electronic Control Device Outdoor Unit MAIN P C B ASM L3 C362LL0 L3 C482LL0 ...
Страница 19: ...Service Manual 19 Electronic Control Device Display P C B ASM ...
Страница 20: ...20 Multi Air Conditioner Schematic Diagram Schematic Diagram Indoor Unit L3 C362LL0 L3 C482LL0 ...
Страница 21: ...Service Manual 21 Schematic Diagram L2 C362LL0 ...
Страница 22: ...22 Multi Air Conditioner Schematic Diagram Outdoor Unit L3 C362LL0 ...
Страница 23: ...Service Manual 23 Schematic Diagram L3 C482LL0 ...
Страница 75: ...P No 3828A20156P January 2005 Printed in Korea ...